Instrukcja obsługi APC RBC23


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla APC RBC23 (1 stron) w kategorii Akumulator. Ta instrukcja była pomocna dla 61 osób i została oceniona przez 6 użytkowników na średnio 4.8 gwiazdek

Strona 1/1
SURM2U Replacement Battery Cartridge installation Guide
This UPS has an easy to replace hot-swappable battery tray. Battery replacement is a safe
procedure, isolated from electrical hazards. You may leave the UPS and the protected equipment
onr tllngprocede. See r dealer or fohe foowi uryou www.apcc.com for more information.
Smart-UPS ModelReplacement Battery Cartridge
SU700M2UR RB22C
SU1000RM2U RBC23
SU1400RM2U RBC24
Pleae sread boepcg etey yefr relainth batrtra:
Once te btery is connced, e cnneeqpent isprefom powerhat disetthocted uim not otcted r otages.u
Battery Replacement Procedure
1.The battery tray is accessible from the front of the UPS.
2.Be careful removing the battery tray – it is heavy.
3.This procedure requires a Phillips head screwdriver.
4.Small sparks at the battery connectors are normal during re-connection.
SU1400M 2URJ J RB 24C
1.Face the front of the UPS and, using both hands, insert each
index finger behind the lip of the curved section of the front
pael bezel ad pll tards. e ot pal bezellnnuow youThfrnne wil
u sn.nap
2.Set te bezel aide.hs
3.Take out the white cord, which is tucked into the space above
the battery connector . Grasp the cord and pull firmly
towards you to disconnect the battery.
4.Use a Phillips head screwdriver to remove the four (4)
screws that secure the battery tray. Set the screws aside.
5.Use the battery tray handle to slide the tray out halfway.
Then hold the tray from the sides and slide it out to the
maximum extended position. A stop tab on the bottom of
te tryll eet e trym cgt clete.ha wiprvntha fro omin ouomply
6.Carefly lt te tryp soat tstptabul if ha u thhe o clearste h
ledge on the unit.
7.Return the battery tray to APC using the package in which
younr repaclemetry spped . ta hi
Thue attery reactit clb pleemn kindes a new battery tray.
8.Hold the new tray on the sides and align it with the opening.
9.Raise the back of the tray up slightly to position the stop tab
on the inside of the opening. Then level the tray and push it
in completely.
10.Remove the tape on the new battery tray connector to expose
the cable connector.
11. Locate the UPS battery connector which is to the right of
the battery tray and recessed. Connect the battery cable
connector to the UPS connector. Press firmly to ensure that
the connection is tight. You will hear a “snapwhen the
connector is properly seated.
12.Replace the four (4) screws removed in step 4.
13.Tuck the white battery cable cord neatly into the space above
the UPS connector.
14.Hold the front panel bezel with the cutout section on the
right. Align the tabs on the side of the bezel with the slots on
the front of the UPS and firmly snap it into place.
990-#### Rev.01 11/01

Oceń tę instrukcję

4.8/5 (6 Recenzje)

Specyfikacje produktu

Marka: APC
Kategoria: Akumulator
Model: RBC23

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z APC RBC23, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Akumulator APC

Apc

APC RBC44 Instrukcja

10 Grudnia 2024
Apc

APC RBC18 Instrukcja

9 Grudnia 2024
Apc

APC RBC24 Instrukcja

9 Grudnia 2024
Apc

APC RBC27 Instrukcja

9 Grudnia 2024
Apc

APC Symmetra LX Instrukcja

16 Września 2024
Apc

APC RBC108 Instrukcja

12 Września 2024
Apc

APC RBC63 Instrukcja

10 Września 2024
Apc

APC RBC142 Instrukcja

7 Września 2024
Apc

APC SRC96XLBP Instrukcja

6 Września 2024
Apc

APC RBC32 Instrukcja

28 Sierpnia 2024

Instrukcje Akumulator

Najnowsze instrukcje dla Akumulator