Instrukcja obsługi Fantini Cosmi L23EM1A


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Fantini Cosmi L23EM1A (2 stron) w kategorii termostat. Ta instrukcja była pomocna dla 18 osób i została oceniona przez 3 użytkowników na średnio 4.4 gwiazdek

Strona 1/2
To get access to the parameter configuration menu, press button + for 5 seconds.
With button select the parameter to be modified. or
Press button to display the value.
By keeping button pressed, use button to set the desired value. or
When button is released, the newly programmed value is stored and the following parameter is displayed.
To exit from the setup, press button or wait for 30 seconds.
PARRANGE DESCRIPTION
SCL 1°C;
2°C;
°F
Readout scale (see table of input specifications)
Caution: upon changing the value, it is then absolutely necessary to the param-SCL reconfigure
eters relevant to the absolute and relative temperatures (, , , etc..)SPL SPH 1SP1HY
SPL -50°...SPHMinimum limit for setting1SP
SPH SPL...150°Maximum limit for setting.1SP
1SP SPL... SPHSetpoint (value to be maintained in the room).
1CM HY; PIDControl mode.
With =H you select control with hysteresis: parameters , are used.1CM Y1HY 1T01T1 and
With =PID you select a Proportional-Integral-Derivative control mode: parameters , , 1CM1PB 1IT
1DT 1AR 1CT, , will be used
1CH REF; HEARefrigerating (REF) or Heating (HEA) control mode.
1CM=HY
1HY 0...19.9°OFF/ON thermostat di ferential. With =0 the output is always of 1HY .
1T0 0...30minMinimum o f time.f
Afteroutputbeenturnedf, itremainsinactiveminutes 1 has of for 1T0 regardless of the
temperature value measured.
1T1 0...30minMinimum on time. ().the following parameter will be 1PF
Afteroutput 1 has beenturned on,it remainsactivefor 1T1 minutesregardless of the temperature
value measured.
1CM=PID
1PB 0...19.9°Proportional bandwidth.
Temperaturetakesby changingcontrol place the
ON of the the closer the timeoutput:temperature
to the the less of setpoint,timeactivation. Asmall
proportional band increases the promptness of
response of the to systemtemperaturevariations,
butmakeitstable. Atends to less purely
proportionalstabilisestemperature control the
withinproportional band butthe does not cancel
the deviation from setpoint.
With =0 the output is always o1PB .
1IT 0...999sIntegral action time.
The error cancelled an steady-stateisby inserting
integral action.integral action time, determines The
the speed the withwhichsteady-statetemperature
is achieved,buthigh(low) may be a speed 1IT the
causeovershootinstability inof and the response.
With =0 the integral control is disabled.1IT
1DT 0...999sDerivative action time.
Response overshootmaybereducedbyinserting
a derivativeAction.A high derivative action(1DT
high) makessystem very sensitive the to small
temperature variationcauses instabilitys and . With
1DT=0 the derivative control is disabled.
1AR 0...100%Reset of integral action time referred to 1PB
Decreasingreducesintegralaction zone,consequentlythe parameter 1AR the control and the
overshoot (see figure on paragraph ).1IT
1CT 1...255s Cycle time.
It’s the the ON changes. The the to controlled period inwhichoutputtimequickersystembe
reacts to the smaller the order to temperaturevariations,cycletimemustbe,inobtainhigher
temperature stability and less sensitivity to load variations.
1PF ON/OFF Output state in case of probe failure.
OAU NON;
THR;
AL0;
AL1
AUX output operation.
NON : output disabled (always o f). (fthe next parameter will be ATM)
THR: output programmed for second thermostat control ().the next parameter will be 2SM
AL0: contacts open when an alarm condition occurs (the next parameter will be ATM).
AL1: contacts make when an alarm condition occurs (the next parameter will be ATM).
OAU=THR
2SM ABS;
REL
Setpoint 2 mode.
Channelma 2et spoint y beab oluste (2SM=ABS , )or a diteren ialterela iv t st oetpoin 1 (2SM=REL)
2SM=ABS
2SP SPL...SPHAuxiliary output switchover temperature ()the next parameter will be 2CH
2SM=REL
2DF -19.9...19.9° Temperature di ferential relative to The auxiliary output setpoint is equal to f1SP. 1SP 2DF+
ON/OFF refrigerating control
( =H1CM Y, =REF)1CH
ON/OFF heating control
( =H1CM Y, =HEA)1CH
1SP1SP+1HY T[°]
ON
OFF
1SP1SP-1HY T[°]
ON
OFF
Time
Temperature
Process
temperature
Overshoot Steady-state error
1PB
1SP
Time
Temperature
Process
temperature
Overshoot
1PB1PBx1AR%
integral control
action area
1SP
Time
Temperature
Process
temperature
Overshoot
1PB
1SP
2SP2SP+2HY T[°]
ON
OFF
2SP2SP-2HY T[°]
ON
OFF
ON/OFF control in refrigeration
(=ABS, =REF)2SM 2CH
ON/OFF control in heating
(=ABS, =HEA)2SM 2CH
1SP+2DF
1SP
2DF>0 1SP+2DF+2HY T[°]
ON
OFF
1SP
1SP+2DF
2DF<0
1SP+2DF-2HY T[°]
ON
OFF
ON/OFF control in refrigeration. Setpoint 2
relative to setpoint 1 (=THR, =REF)OAU 2CH
ON/OFF control in heating. Setpoint 2
relative to setpoint 1 (=THR, =HEA)OAU 2CH
Power supply
L03BI- 12Vac/dc ±10%, 3W
L03BM- 230Vac±10%, 50/60Hz, 3W
Relay outputs (L03B---)
OUT116(4)A 240Vac
OUT216(4)A 240Vac
Inputs
see table of input specifications
Measurement range
see table of input specifications
Measurement accuracy
see table of input specifications
Operating conditions
-10 … +50°C; 15%...80% r.H.
CE (Reference Norms)
EN60730-1; EN60730-2-9;
EN55022 (Class B); EN50082-1
Front protection
IP40
OAU=THR
2CH REF; HEARefrigerating control (REF) or heating control mode (HEA) for the auxiliary output.
2HY 0...19.9°Di ferential of thermostat 2. With =0 the auxiliary output always remains of2HY .
2T0 0...30minMinimum o f time.f
Afteroutput2 has beenturnedof f, itremainsinactivefor 2T0minutesregardless of the temperature
value measured.
2T1 0...30minMinimum on time.
Afteroutput2 has been turned on, it remains active for 2T1 minutes regardless of the temperature
value measured.
2PF ON/OFF Auxiliary output state in case of probe failure.
ATM NON;
ABS;
REL
Alarmhrehold managemen ts t.
NONt : allempera ture alarmsareed inhibit (t t heollowing fparame erwillbe SB).
ABS: t vhe alues programmed inALA A and AH s srepreenhet treal alarmhre tholds.
REL: theprogrammed values inALR andAHR arealarm diffteren ials tre erredfo 1SPand 1SP Y+1H .
ATM=ABS
ALA -50°...AHALow temperature alarm threshold.
AHA ALA...15High temperature alarm threshold.
ATM=REL
ALR -12.0...0°Low temperature alarm di ferential. f
With =0 the low temperature alarm is excludedALR
AHR 0...12.0°High temperature alarm di ferential. f
With =0 the high temperature alarm is excludedAHR
ATD 0...120minDelay before alarm temperature warning.
SB NO/YESStand-by button enabling.
INP 0mA/4mA,
T1/T2
ST1/SN4
Sensor input selection (see table of input specifications).
Warning: “0mA/4mA”, “T1” and “T2” are not available
RLO -19.9...RHIMinimum range value
RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V, 0/4mA).
RHI RLO...99.9Maximum range value
RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V, 20mA)
OS1 -12.5...12. T1 oset.Probe
TLD 1...30minDelay for minimum temperature (TLO) and maximum temperature (THI) logging.
SIM 0...100Display slowdown
ADR 1...255 address for PC communication (not available)
1SP
1SP-ALR
T[°]
ON
OFF
1SP+1HY+AHR
1SP1SP-1HY-ALR 1SP+AHR
T[°]
ON
OFF
Temperature alarm with relative thresholds,
refrigerating control (ATM 1CH=REL, =REF)
Temperature alarm with relative thresholds,
heating control (ATM 1CH=REL, =HEA).
DISPLAY
During normal operation, the display shows either the temperature measured or one of the following indications:
Controller in stand-byController in autotuning
Probe T1 overrange or failureIn tuning: timeout1 error
Room high temperature alarmIn tuning: timeout2 error
Room low temperature alarm In tuning: overrange error
MENU INFO
The information available in this menu is:
Maximum temperature recordedKeypad state lock
Minimum temperature recorded
Access to menu and information displayed.
Press and immediately release button .
With button select the data to be displayed. or
Press button to display value.
To exit from the menu, press button or wait for 10 seconds.
Reset of THI, TLO recordings
With button select the data to be reset. or
Display the value with button .
While keeping button pressed, use button .
CHANNEL 1 SETPOINT (display and modification of desired temperature value)
P se reandss relea
bu
tt
on
L : the
ED s1L1 blinks, the di play shows SP 1ec etaoct for sond andhenhe t t spoint ssia ed value.
P ressbuttons o or tsehet tdesired value (adjusis witment thin minimum the SPL andmaximum SPHtlimi ).
To store the new value press button , or wait for 10 seconds.
To go back to normal mode without saving the new value, press .
CHANNEL 2 SETPOINT
Withauxiliary output(the set as thermostat control =THR),itpossiblemodifysetpointduringoperation OAU ’s to 2 the normal
of the controller.
Press and release button : LEDL2blinks, displayshows2Sifsetpointisabsolutethe the P for 1 second 2 an threshold
(=ABS), alternativelydisplayshows2SM the 2DF,ifsetpointisrelativesetpoint(=REL),value 2 a threshold to 1 2SM then the
associated to the parameter appears.
Press buttons to set the desired value. or
To store the new value press button or wait for 10 seconds.
To go back to normal mode without saving the new value, press .
STAND-BY
B
u
ttss fon , when preedor 3secondheonrollers, allows t ct to be put on a standby torou put tconrolto be resumed (wi th SB=YES only).
KEYPAD LOCK
The attempted the controllers keypad lock avoidsundesired,potentially dangerous operations, which might bewhenis operating
in publicmenu,=YESinhibitfunctionsbuttons. a place. In the INFO set parameter LOC to all of the To normal resumeoperation
of keypad, adjust setting so that LOC=NO.
CONTROLLER AUTOTUNING IN PID MODE
Before starting
In the mode set =PID; that matches the mode setup(see configuration parameters):1CM make sure1CH desired operation
(=REF for refrigerating control, =HEA for heating control); then adjust setpoint at the desired value.1CH 1CH1SP
Start autotuning
Duringoperation,keepbuttons 3blinksdisplay normal + pressed for seconds. 1CT on the . + or set the With cycle
time indefinedynamicbe order to the of the process to controlled. To the press ; to start abortautotuning function,autotuning
press + or wait for 30 seconds.
During autotuning
Duringentireautotuningphase,displayTUNwithactualtemperaturemeasured.powerfailure, the the alternates the In case of
when power isresumed,initial autotest phase,resumesautotuning function. after the the controller the To the abortautotuning,
withoutmodifyingpreviousparameters,keepbutton the control pressed for seconds. the has place 3After autotuningtaken
successfully, the controller updates the control parameters and start to control.
Errors
If the autotuning function failed, the display shows an error code:
E1 the controller not the the Increase timeout1 error:couldbringtemperature withinproportional band.inheating 1SP case of
control, vice versa, decrease in case of refrigerating control and re-start the process.1SP
E2 the has not ended the Re-start the timeout2error:autotuningwithinmaximumtime allowed(1000 cycletimes).autotuning
process and set a longer cycle time 1CT.
E3 temperature overrange: checkwascaused byprobe malfunction, that the error not a then decrease inheating 1SP case of
control, vice versa increase in case of refrigerating control and then re-start the process.1SP
To eliminate the error indication and return to the normal mode, press button .
Control improvement
To reduce overshoot, reduce the integral action reset 1AR
To increasethe
response speed
o
f t theem syst, reduce
he propor
t
ional band
.e
To reduce swings in steady-state temperature,increaseintegral actiontime the
system stability1IT;
is thus increased, although
its response speed is decreased.
To the speed of response to the the increasevariationsintemperature,increasederivativeactiontime Caution:high 1DT. a
value makes the system sensitive to small variations and it may be a source of instability.
RECALIBRATION
Have a precision reference thermometer or a calibrator to hand. Ensure that =0 and =0.OS1 SIM
Switch the controller o f then on again.f
During the auto-test phase, press buttons and keep them pressed till the controller shows + 0AD.
With buttons : allowscalibration0, insertingcorrection overwhole and select or 0ADSAD 0AD a of a constant the scale
of a of the top part of the scale a the measurement. SAD allowscalibrationmeasurementwithproportional correction between
calibration point and 0.
Press to the and then + or to the read the the display valueuse makevaluecoincide withvaluemeasured by
reference instrument.
Exit from calibration by pressing button .
The
L03B--
controller
, size 71x98x61(WxHxD), isbesecuredrail in suchpositionensureliquid mm to to a DIN a as to that no
infiltrates causing serious damage and compromising safety;
Make sureelectrical connectionscomplywith“wiring diagrams”. that the paragraph To the eects of reduceelectromagnetic
disturbance, keep the sensor and signal cables well separate from the power wires.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
OUT1
OUT2
L1
L2
Channel 1 output
Channel 2 output
Alarm
Channel 1 setpoint modification
Channel 2 setpoint modification
Fig.1 - Front panel
Thank you for having chosen a Fantini Cosmi product. Before installing the instrument, please read these instructions carefully
to ensure maximum performance and safety.
L03B--/L23EM1A INSTRUCTION FOR USE
Info / Enter buttonModify Setpoint 1 / Decrease button
Increase / Modify Setpoint 2 buttonExit / Stand-by button
MODEL INPUT
RANGE [MEASUREMENT ACCURACY]
SCL=1°C SCL=2°CSCL=°F
L03B--
INP=ST1 PTC 1000 Ω
(LS120)
-40/-19.9 ÷ 99.9/105°C
[<±0.3°C(-40÷130°)C]
-40 ÷ 105°C
[<±0.3°C (-40÷130°),±1°C]
-40 ÷ 221°F
[<±0.6°F (-40÷221°),±2°F]
INP=SN4 NTC 10K Ω
(LS130)
-40/-19.9 ÷ 99.9/105°C
[<±0.3°C(-40 100÷°), ±1°C]
-40 ÷ 105°C
[<±0.3°C (-40÷100°),±1°C]
-40 ÷ 221°F
[<±0.6°F (-40÷210°),±2°F]
Via Dell’Osio 6
20090 Caleppio di Settala MI ITALIA
Phone no. +39 02 95682.222
Fax no. +39 02 95307006
Web: www.fantinicosmi.it
e-mail: export@fantinicosmi.it
AC1-5
L03BI--
1112
12Vac/dc
OUT2
1817 16
OUT1
21 20 19
2 3
16(4)A16(4)A
L23EM1A
12 11
230V~
OUT1
21 20 19
rH
V
2 34
VIN V+V-
16(4)A
L23EM1A 0÷1V (LS160A)RLO÷RHI [< ± 3mV]-----

Oceń tę instrukcję