Safety
Specifications
Connect the Battery
The Back-UPS is shipped with one battery cable disconnected. Remove the “Stop! 
Connect the Battery” label that covers the outlets. Prior to connecting any equipment 
to the unit, connect the battery cable to the unused battery terminal. It is normal for 
small sparks to be seen when the battery cable is connected to the battery terminal.    
Wall Mount Installation
• Horizontal installation, use 2 screws 5.0" (127 mm) apart. 
• Vertical installation, use 2 screws 4.3" (110.4 mm) apart. 
• Allow 5/16" (8 mm), of the screw to protrude from the wall.
Connect Equipment
Battery Backup + Surge Protection Outlets
Battery backup outlets provide protection to connected equipment when the 
Back-UPS is turned on and connected to utility power.
Battery backup outlets receive power from the Back-UPS for a limited period of time 
when a power outage, or brownout condition occurs.
Battery backup outlets provide protection from power surges or spikes.
Connect a computer, monitor and other peripheral devices to the outlets.
Surge Protection Outlets
Surge protection outlets provide protection to connected equipment when the 
Back-UPS is connected to utility power, and is switched on or off.
Surge protection outlets provide protection from power surges or spikes.
Connect a printer, scanner or other peripheral devices that do not need to remain on 
during power outages, or utility problems to the surge protection outlets.
Connect Network
The Back-UPS protects equipment connected to a 10/100 Base-T ethernet, from 
power surges when connected through the Back-UPS coaxial connectors.
Turn On the Back-UPS
Press the POWER ON button located on the top of the Back-UPS. The Power On/
Replace Battery LED will illuminate and a single short beep will be audible to 
indicate that the Back-UPS is providing protection for connected equipment.
The Back-UPS battery charges fully during the first 16 hours while connected to 
utility power. The Back-UPS battery will charge while the Back-UPS is switched on 
or off and is connected to utility power. Do not expect full battery run capability 
during the initial charge time. 
If the red Building Wiring Fault LED located on the side of the Back-UPS 
illuminates, do not operate the Back-UPS. Have a qualified electrician correct the 
building wiring fault.
Voltage Sensitivity Adjustment (optional)
The Back-UPS detects and reacts to line voltage distortions by transferring to battery 
backup power to protect connected equipment. In situations where either the Back-
UPS or the connected equipment is too sens tage level it is itive for the input vol
necessary to adjust the transfer voltage.
1. Connect the Back-UPS to a wall outlet. The Back-UPS will be in Standby mode, 
no indicators will be illuminated.
2. Press and hold the ON/OFF button for 10 seconds. The OnLine LED will 
illuminate alternately green-amber-red, to indicate that the Back-UPS is in 
Program mode.
3. The Power On/Replace Battery LED will flash either green, amber, or red to 
indicate the current sensitivity level. Refer to the table for an explanation of the 
transfer voltage sensitivity levels.
4. To select LOW sensitivity, press and hold the ON/OFF button until the LED 
flashes green.
5. To select MEDIUM sensitivity, press and hold the ON/OFF button until the LED 
flashes red.
6. To select HIGH sensitivity, press and hold the ON/OFF button until the LED 
flashes amber.
7. To exit Program mode wait five seconds and all LED indicators will extinguish. 
Program mode is no longer active.
This unit is intended for indoor use only. 
Do not operate this unit in direct sunlight, in 
contact with fluids, or where there is 
excessive dust or humidity.
Connect the Back-UPS power cord directly to 
a wall outlet. Do not use a surge protector or 
an extension cord.
Input
Voltage 120 Vac Nominal
Frequency 60 Hz + 3
Brownout Transfers 92 Vac Typical
Over-voltage Transfer 139 Vac Typical
Output
UPS Capacity 
(3 outlets) 350 VA, 200 W 
Total Amperage 
(6 outlets) 8 A (including UPS output)
Voltage - On Battery 115 Vac ± 8%
Frequency - On Battery 60 Hz + 1
Transfer Time 6 ms Typical, 10 ms maximum
Protection 
and 
Filtering
AC Surge Protection Full time, 340 Joules
EMI/RFI Filter Full time
AC Input Resettable circuit breaker
Battery
Type Sealed, maintenance-free, lead acid 
Replacement battery cartridge RBC35
Average Life 3 - 5 years depending on the number 
of discharge cycles and environmental 
temperature
Physical
Net Weight 9 lb (4 kg)
Dimensions 
Length x Width x Height 11 in x 6 in x 3 in
29 cm x 16 cm x 9 cm
Operating Temperature 32º F to 104º F (0º C to 40º C)
Storage Temperature 5º F to 113º F (–15º C to 45º C)
Operating Relative Humidity 0 to 95% non-condensing humidity
Operating Elevation 0 to 10,000 ft (0 to 3000 m)
EMC 
Compliance
This device complies with part 68 and part 15 of the FCC rules. 
Operation is subject to the following two conditions: (1) This device 
may not cause harmful interference, and (2) This device must accept 
any interference received, including interference that may cause 
undesired operation.
 Press the battery compartment cover 
release tab located on the rear side of the 
unit. Slide the battery cover off.
 Connect the battery cable securely to 
the battery terminal.
 Reinstall the battery compartment 
cover. Be sure that the release tab locks 
into place.
bu064a
bu065a
bu066a
LED 
Flashes
Sensitivity 
Setting
Input Voltage Range
(Utility Operation) Recommended Use
Green LOW 88 Vac to 142 Vac Use this setting with equipment that 
is less sensitive to fluctuations in 
voltage or waveform distortions.
Red MEDIUM 92 Vac to 139 Vac Factory default setting. Use this 
setting under normal conditions.
Amber HIGH 96 Vac to 136 Vac Use this setting when connected 
equipment is sensitive to voltage 
and waveform fluctuations.
bu206a
Back-UPS 
Battery Backup + 
Surge Protection 
Surge Protection 
bu208a
CAUTION-Refer to bottom
of unit for safety markings.
Circuit
Breaker
Building
Wiring Fault
Network
Out
Push to
Reset
Network
In
User Manual Back-UPS® BE350G Series
Specyfikacje produktu
| Marka: | APC | 
| Kategoria: | UPS | 
| Model: | BE350G-CN | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z APC BE350G-CN, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS APC
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         30 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         27 Marca 2025
                        
                    
                                                            
                        
                         27 Marca 2025
                        
                    
                                                            Instrukcje UPS
- Avocent
- Digitus
- Altronix
- Hikvision
- Gembird
- V7
- Phoenix Contact
- LevelOne
- Energenie
- PowerWalker
- Vanson
- Minuteman
- FSP
- Dell
- FSP/Fortron
Najnowsze instrukcje dla UPS
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         5 Marca 2025
                        
                    
                                                            
                        
                         5 Marca 2025
                        
                    
                                                            
                        
                         30 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         27 Stycznia 2025