CP1500PFCRM2U
USER MANUAL
Cyber Power Systems (USA), Inc. 4241 12th Avenue East, Suite 400 | Shakopee, MN 55379 | CyberPowerSystems.com
IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS)
When using electrical appliances, basic safety precautions should always be followed to 
reduce the risk of fire, electric shock, and/or injury to persons including the following. This 
Manual Contains Important Instructions that should be followed during installation and 
maintenance of the UPS and batteries.
CAUTION!  To prevent the risk of fire or 
electric shock, install in a temperature 
and humidity controlled indoor area free 
of conductive contaminants.  (Please see 
specifications for acceptable temperature 
and humidity range).
CAUTION!  To reduce the risk of electric 
shock, do not remove the cover except to 
service the battery. Turn off and unplug the 
unit before servicing the batteries. There 
are no user serviceable parts inside except 
for the battery.
CAUTION!  Hazardous live parts inside can 
be energized by the battery even when the 
AC input power is disconnected.
CAUTION!  The UPS must be connected 
to an AC power outlet with fuse or circuit 
breaker protection. Do not plug into an 
outlet that is not grounded.  If you need to 
de-energize this equipment, turn off and 
unplug the unit.
CAUTION!  To avoid electric shock, turn off 
the unit and unplug it from the AC power 
source before servicing the battery.
CAUTION!  Not for use in a computer 
room as defined in the Standard for the 
Protection of Electronic Computer/Data 
Processing Equipment, ANSI/NFPA 75.
CAUTION!  To reduce the risk of fire, 
connect only to a circuit provided with 
20 amperes maximum branch circuit over 
current protection in accordance with the 
National Electric Code, ANSI/NFPA 70.
DO NOT USE FOR MEDICAL OR LIFE 
SUPPORT EQUIPMENT!  CyberPower 
Systems does not sell products for life 
support or medical applications.   DO NOT
use in any circumstance that would affect 
the operation and safety of life support 
equipment, medical applications, or patient 
care.
DO NOT USE WITH OR NEAR 
AQUARIUMS!  To reduce the risk of fire 
or electric shock, do not use with or near 
an aquarium. Condensation from the 
aquarium can cause the unit to short out.
DO NOT USE THE UPS ON ANY 
TRANSPORTATION! To reduce the risk of 
fire or electric shock, do not use the unit 
on any transportation such as airplanes 
or ships. The effect of shock or vibration 
caused during transit and the damp 
environment can cause the unit to short 
out.
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt. The box 
should contain the following:
(a) UPS 
(b) User’s manual 
(c) USB A+B type cable 
(d) Function Setup Guide
(e) M5 truss head screw x4pcs
*PowerPanel® Business software is 
available on our website. Please visit 
cyberpowersystems.com and go to the 
Software Section for free download.
SUPPORTS ACTIVE PFC POWER 
SUPPLIES
This CyberPower UPS system delivers sine 
wave output, which is ideal for seamless 
operation of computers using high 
efficiency switching power supplies with 
Active Power Factor Correction(Active 
PFC), home entertainment systems, and 
other sensitive electronics.
OVERVIEW
The CP1500PFCRM2U provides complete 
power protection from utility power 
that is not always consistent. The 
CP1500PFCRM2U features 1500 Joules 
of surge protection. The unit provides 
long lasting battery backup during power 
outages with maintenance free batteries. 
The CP1500PFCRM2U ensures consistent 
power to your electronic devices and 
includes software that will automatically 
save your open files and shutdown your 
computer system during a utility power 
loss.
AUTOMATIC VOLTAGE REGULATOR
The CP1500PFCRM2U stabilizes 
inconsistent utility power voltage to 
nominal levels that are safe for equipment. 
Inconsistent incoming utility power may 
be damaging to important data files and 
hardware, but with Automatic Voltage 
Regulation (AVR), damaging voltage 
levels are corrected to safe levels.  AVR 
automatically increases low utility power 
to a consistent and safe 110/120 volts.
DETERMINE THE POWER REQUIREMENTS 
OF YOUR EQUIPMENT
1.  Ensure that the equipment plugged 
into the outlet does not exceed the 
UPS’s rated capacity (1500VA/1000W 
for CP1500PFCRM2U). If the rated 
capacity of the unit is exceeded, an 
overload condition may occur and 
cause the UPS to shut down or the 
circuit breaker to trip.  
2.  There are many factors that can 
affect the amount of power that your 
electronic devices will require. It is 
suggested that the load placed on the 
battery outlets not exceed 80% of the 
unit’s capacity. REMINDER:  Batteries are considered HAZARDOUS WASTE and must be disposed of properly.  Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by 
local regulations
K01-0000960-01
1.  LCD module display 
High resolution and intelligent LCD 
display shows all the UPS information 
using icons and messages. For 
more information, please review 
the “Definitions for Illuminated LCD 
indicators” section.
2.  Power On Indicator 
This LED is illuminated when the utility 
power is normal and the UPS outlets 
are providing power, free of surges and 
spikes.
3.  Power Switch 
Master on/off switch for equipment 
connected to the battery power 
supplied outlets.
4.  Down/Display button 
The button can be used to select the 
LCD display contents including Input 
Voltage, Output Voltage, and Estimated 
Run Time. Short press the button to 
scroll down the function menu. Pressing 
the button for 2 seconds will keep the 
LCD display always on or turn the LCD 
display off while in AC/Utility power 
mode. For more information about the 
Down/Display Button, please refer to 
the Function Setup Guide.
5.  Up/Mute button 
Short press the button to scroll up the 
function menu. Holding the button for 
more than 2 seconds will silence the 
alarm. For more information about the 
Up/Mute Button, please refer to the 
Function Setup Guide.
6.  Enter/Setup Button 
Press the button for 2 seconds to enter 
the setup menu and then select the 
functions for configuration. For more 
information about the Enter/Setup 
Button, please refer to the Function 
Setup Guide.
7.  Circuit Breaker 
Located on the back of the UPS, 
the circuit breaker serves to provide 
overload and fault protection. Under 
normal operating conditions, the circuit 
breaker is depressed.
8. Expansion Slot 
Remove the cover panel to install an 
optional RMCARD to remotely monitor 
and manage the UPS over a network. 
Other options include cloud monitoring 
via a mobile app and web-based app 
(RCCARD or RWCCARD).
9. Communication Protection Ports RJ45 
Communication protection ports, 
bi-directional, will protect a 
10/100/1000Ethernet connection. 
(RJ45).
10.  Battery and Surge Protected Outlets 
The unit has eight battery powered/
surge suppression outlets for 
connected equipment to ensure 
temporary uninterrupted operation of 
your equipment during a power failure. 
(DO NOT plug a laser printer, paper 
shredder, copier, space heater, vacuum 
cleaner, sump pump or other large 
electrical devices into the “Battery 
and Surge Protected Outlets”. The 
power demands of these devices may 
overload and damage the unit.)
11.   Wiring Fault Indicator (Red) 
This LED indicator will illuminate to 
warn the user that a wiring problem 
exists, such as bad ground, missed 
ground or reversed wiring. If this is 
illuminated, disconnect all electrical 
equipment from the outlet and have an 
electrician check to ensure the outlet 
is properly wired. The unit will not 
provide surge protection without being 
plugged into a grounded and properly 
wired wall outlet.
12.  Dry contact 
This port produces information for 
equipment that can read dry contact 
signals.
13.  USB Port to PC 
This port allows connection and 
communication from the USB port 
on the computer to the UPS unit. The 
UPS communicates its status to the 
PowerPanel® Business software.
14.  Widely Spaced Outlets Designed for 
AC Adapters 
The unit has two outlets spaced to 
allow AC power adapter blocks to be 
plugged into the UPS without blocking 
adjacent outlets.
BASIC OPERATION
1.  Your new UPS may be used 
immediately upon receipt. However, 
after receiving a new UPS, to ensure 
the battery’s maximum charge capacity, 
it is recommended that you charge the 
battery for at least 8 hours. Your UPS is 
equipped with an auto-charge feature. 
When the UPS is plugged into an AC 
outlet, the battery will automatically 
charge whether the UPS is turned on or 
off. 
Note: This UPS is designed with a 
safety feature to keep the system from 
being turned on during shipment. The 
first time you turn the UPS on, you will 
need to have it connected to AC power 
or it will not power up.
2.  With the UPS unit turned off and 
unplugged, connect your computer, 
monitor, and any other peripherals 
requiring battery backup into the 
battery power supplied outlets. DO 
NOT plug a laser printer, paper 
shredder, copier, space heater, 
vacuum, sump pump or other large 
electrical devices into the “Battery 
and Surge Protected Outlets”. The 
power demands of these devices may 
overload and damage the UPS.
3.  Plug the UPS 
into a 2 pole, 3 
wire grounded 
receptacle (wall 
outlet). Make sure 
the wall branch outlet is protected by 
a fuse or circuit breaker and does not 
service equipment with large electrical 
demands (e.g. air conditioner, copier, 
etc…). The warranty prohibits the use 
of extension cords, outlet strips, and 
surge strips.
4.  Press the power switch to turn the 
unit on. The Power On indicator light 
will illuminate and the unit will “beep”. 
If an overload is detected, an audible 
alarm will sound and the unit will emit 
one long beep. To correct this, turn the 
UPS off and unplug at least one piece 
of equipment from the battery power 
supplied outlets. Make sure the circuit 
breaker is depressed and then turn the 
UPS on.
5.  To maintain optimal battery charge, 
leave the UPS plugged into an AC 
outlet at all times.
6.  To store the UPS for an extended 
period, cover it and store with the 
battery fully charged. While in storage, 
recharge the battery every three 
months to ensure battery life.
7.  Ensure the wall outlet and UPS are 
located near the equipment being 
attached for proper accessibility.
INSTALLING YOUR UPS SYSTEM - Continued 
HARDWARE INSTALLATION GUIDE
PRODUCT REGISTRATION
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at: cyberpowersystems.com/registration. Registration certifies your product's warranty, 
confirms your ownership in the event of a product loss or theft and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership.
Replacement of batteries located in an OPERATOR ACCESS AREA. 
1.  When replacing batteries, replace with the same number of the following battery: 
CyberPower / RB1290X2D
2.   Risk of Energy Hazard, 24 V, maximum 9 Ampere-hour battery. Before CAUTION!
replacing batteries, remove conductive jewelry such as chains, wrist watches, and 
rings. High energy conducted through these materials could cause severe burns.
3.   Do not dispose of batteries in a fire. The batteries may explode.CAUTION!
4.   Do not open or mutilate batteries. Released material is harmful to the skin CAUTION!
and eyes. It may be toxic.
5.   A battery can present a risk of electrical shock and high short circuit CAUTION:
current. The following precautions should be observed when working on batteries:
1) Remove watches rings, or other metal objects.
2) Use tools with insulated handles.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. 
DISPOSE OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS.
REPLACING THE BATTERY BATTERY REPLACEMENT PROCEDURE:
1.  Loosen the screws on the faceplate.
2.  Slide the side front panel.
3.  Remove front panel completely off the unit.
4.  Disconnect the black and red cable.
5.   Replace the new battery pack. Assemble the screws, covers, cable and front panel in 
the reverse sequence of above steps. 
Recharge the units for 8-16 hours to ensure the UPS performs expected runtime.
FEATURES
1  . LCD module display
2 . Power On Indicator
3 . Power Switch
4 . Down/Display button
5 . Up/Mute button
6 . Enter/Setup Button
7 . Circuit Breaker
8 . Expansion Slot
9 . Communication Protection Ports RJ45
10 . Battery and Surge Protected Outlets
1 1 . Wiring Fault Indicator (Red)
12 . Dry contact
13 . USB Port to PC
14 . Widely Spaced Outlets Designed for AC Adapters
1. 
4.  5. 
2.  3. 
5
9
11 12
87 10
13 14
6
31 42
RACK INSTALLATION (OPTION)
1.  Remove all equipment connected to the product.
2.  Make sure the product is turned off and 
disconnected from AC power source.
3.  Use the supplied truss head screws to secure the 
UPS to your existing rack system. 
Specyfikacje produktu
| Marka: | CyberPower | 
| Kategoria: | UPS | 
| Model: | CP1500PFCRM2U | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z CyberPower CP1500PFCRM2U, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS CyberPower
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         27 Stycznia 2025
                        
                    
                                                            
                        
                         27 Stycznia 2025
                        
                    
                                                            
                        
                         15 Stycznia 2025
                        
                    
                                                            
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         30 Grudnia 2025
                        
                    
                                                            Instrukcje UPS
- Online USV
- Minute Man
- V7
- Gembird
- Voltcraft
- Conceptronic
- Vanson
- GYS
- Emerson
- FSP
- Approx
- Bxterra
- Dell
- Liebert
- Phoenix Contact
Najnowsze instrukcje dla UPS
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         30 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         27 Marca 2025