Instrukcja obsługi CyberPower Smart App Sinewave PR500LCDRT1U
                    CyberPower
                    
                    UPS
                    
                    Smart App Sinewave PR500LCDRT1U
                
                                
    Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla CyberPower Smart App Sinewave PR500LCDRT1U (2 stron) w kategorii UPS. Ta instrukcja była pomocna dla 9 osób i została oceniona przez 5 użytkowników na średnio 4.9 gwiazdek
                        Strona 1/2
                    
                    
                    
Smart App Sinewave Series 
PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U 
User’s Manual 
                                                                K01-0000323-01
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read 
and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, 
or operate. 
CAUTION!    The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an 
outlet that is not grounded.    If you need to de-energize this equipment, turn off and unplug the UPS.   
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!         CyberPower
Systems does not sell products for life support or 
medical applications. DO NOT use in any  circumstance  that would affect operation or safety of  any life support equipment, with any medical 
applications, or patient care. 
CAUTION!    The battery can energize hazardous live parts inside even when the AC input power is disconnected. 
CAUTION!    For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily accessible. 
CAUTION!    To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area,  free  of  conductive 
contaminants. Please see specifications for acceptable temperature and humidity range. 
CAUTION!    To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no serviceable parts inside, 
except for the battery. 
CAUTION!    To  avoid  electrical  shock,  turn  off  the unit and  unplug  it  from  the  AC  power  source  before  servicing  the  battery  or  installing  a 
computer component. 
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!         To reduce the risk of fire, do not use with or near aquariums.    Condensation from 
the aquarium can come in contact with metal electrical contacts and cause the machine to short out. 
CAUTION!    DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS. 
UNPACKING 
Inspect the UPS upon receipt. The box should contain the following. 
(1) UPS Unit; (1) User's Manual for UPS; (2) Rack Mount Brackets; (2) Wall Mount Brackets; (2) Stands (1) Emergency Power Off Cable (gray) (1) 
PowerPanel® Business Edition Software CD; (1) Serial Interface Cable (RJ45/DB-9); (1) USB A+B type cable; (1) Warranty Registration Card. 
OVERVIEW 
The   provides  automatic  voltage  regulation  for   PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
inconsistent  utility power.  The features  1030  Joules  PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U 
of  surge  protection,  and  provides  battery  backup  during  power  outages.  The  PR500LCDRT1U 
/PR750LCDRT1U/PR1000LCDRT1U ensures  consistent power to your computer system  and its included 
software will automatically save your open files and shutdown  your computer system during a utility power 
loss. 
AUTOMATIC VOLTAGE REGULATOR(AVR) 
The      stabilizes inconsistent utility power. The incoming utility power may be damaging to PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
important data and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic 
Voltage  Regulator automatically increases low  or  decreases high  voltage  to a  consistent, computer  safe 110/120V. The  unit  powerful sealed 
lead-acid batteries will provide power only if the incoming voltage drops below 80v or increases above 150V. 
SYSTEM BLOCK DIAGRAM 
HARDWARE INSTALLATION GUIDE 
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours 
is  recommended  to  ensure  that  the  battery's  maximum  charge  capacity  is  achieved.  Charge  loss  may  occur 
during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will 
charge in both the on and off position.   
2. If you will use the software, connect the serial interface cable to the serial port on the UPS and the computer. If 
you would like to use USB cable, please connect the USB cable on the UPS then connect the USB cable to your 
computer.   
3. With  the  UPS  unit  off  and  unplugged,  connect  your  computer, monitor,  and  any  externally  powered  data 
storage  device  (Hard  drive,  Tape  drive, etc.)  into  the  battery  power  supplied  outlets.    DO  NOT  plug  a  laser 
printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power 
demands of these devices will overload and possibly damage the unit. 
4. Plug the  UPS into a  2 pole,  3 wire grounded receptacle  (wall outlet).    Make  sure the wall branch  outlet is 
protected  by a fuse  or circuit breaker and  does  not service  equipment with large  electrical  demands  (e.g. air 
conditioner, refrigerator, copier, etc.). Avoid using extension cords. 
5. Depress  the power switch to  turn the  unit  on. The  power on  indicator light will illuminate. If an  overload  is 
detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and 
unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the 
circuit breaker is depressed and then turn the UPS on. 
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 
7. To store  your UPS for an extended period, cover it and store with the battery fully charged.    Recharge the 
battery every three months to ensure battery life. 
8. Professional Rack Mount UPS provides one RJ45 and one USB port to allow connection and communication 
between the UPS and computers  or  equipment. The  Primary  computers (with PowerPanel® Business Edition 
installed) are the computers that you will use to control the UPS and make any changes to the operation of the 
UPS. When there is a power failure, the computer which connects to Primary port will start to shutdown after a 
user  controlled delay.  PowerPanel® Business  Edition will save  and close  any open files prior to  shutting  the 
system down. 
9. EPO (Emergency Power Off) Port: 
The feature is for the application to enable emergency power shutdown. Use the gray cable provided to connect 
the UPS to a normally closed or normally open contact switch according to the circuit diagram. EPO function is 
provided in the UPS. EPO remote  switch which  is  a Push-Back  button installed computer  room outside  by a 
phone line and not connected any other equipment. 
FRONT / REAR PANEL DESCRIPTION 
1  Power Switch.  
Master on/off switch for equipment connected to the UPS. 
2. Power On Indicator 
Indicates the power is on.   
3. LCD Module Display 
LCD shows all the UPS information with icons and messages. 
4  LCD Display Toggle Button .
The button can be used to toggle between different data displays   
on the LCD.   
5 Battery Backup and Surge Protected Outlets . 
Provides six battery powered, surge protected and AVR outlets 
for connected  equipment and  ensures  temporary uninterrupted 
operation of connected equipment during a power failure. 
Surge Only 
Surge  only  outlet  provide surge protection  without backup and 
AVR function. 
Critical /Non-critical   
When the UPS is overloaded, the circuit breakers will be tripped 
to  interrupt  the  power  supply  to  the uncritical  outlets  while 
continuing to  supply the  critical  outlets. As well, as  the  battery 
capacity depletes under the threshold value, the uncritical outlets 
will be  shut  down  and  provide  energy  for  critical  outlets.  The  
threshold  can  be  determined  and  set  by  users.  Non-critical 
outlets can also be turned on/off manually through the software 
package provided.  
6  Input Power Cord .
Heavy-duty, extra long power cord. 
7  Input Circuit Breaker .
Resettable  circuit  breakers  provide  Input  optimal  overload 
Protection. 
Contact your dealer, or email tech@cpsww.com. Refer to replacement battery pack number   for  ,  for RB0690X2A PR500LCDRT1U RB0670X4A 
PR750LCDRT1U RB0690X4B PR1000LCDRT1U and   for  . 
Read  and  follow  the  IMPORTANT  SAFETY  INSTRUCTIONS  before  servicing  the  battery.    Service  the  battery  under  the  supervision  of 
personnel knowledgeable of batteries and their precautions. Servicing the battery should only be performed by trained personnel. 
Replacement of batteries located in an OPERATOR ACCESS AREA. 
CAUTION!    When replacing batteries, replace with the same number of the following battery:   for HR9-6FR(BB) PR500LCDRT1U and 
PR1000LCDRT1U,BP7-6FR(BB) for PR750LCDRT1U. 
CAUTION!    Risk of Energy Hazard, 6V, maximum 8 Ampere-hour batteries. Before replacing batteries, remove conductive jewelry such as 
chains, wrist watches, and rings. High energy through conductive materials could cause severe burns. 
CAUTION!    Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions. 
CAUTION!    To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in 
accordance with the National Electric Code, ANSI/NFPA 70. 
CAUTION!    Use only the specified type of battery. See your dealer for replacement batteries. 
CAUTION!    The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local 
ordinances regarding proper disposal of batteries. 
CAUTION!    Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic. 
CAUTION!    A battery can present a high risk of short circuit current and electrical shock. 
Take the following precautions before replacing the battery: 
1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. Do not lay tools or metal parts on top of battery or any terminals. 
4. Wear rubber gloves and boots. 
5. Determine  if the  battery  is inadvertently grounded.    If inadvertently grounded,  remove source of ground. CONTACT WITH  A GROUNDED 
BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation 
and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit) 
BATTERY REPLACMENT PROCEDURE: 
Line mode 
Select SW
Press 
UPS Status Display  Capacity Display  Digital Value Display 
      Load 
Cap 
Battery
Cap 
Input 
Voltage
Output 
Voltage
Run 
Time 
% of 
Load 
% of 
Battery 
Initial  V  X  --  X    V  V         
1st  V  X  --  X    V    V       
2nd
  V  X  --  X  V          V   
3rd  V  X  --  X    V          V 
4th  V  X  --  X          V     
5th
(return)  V  X  --  X    V  V         
(overload)  V  X  --  V  --  --  --  --  --  V  -- 
Battery Mode 
Select SW 
Press 
UPS Status Display  Capacity Display  Digital Value Display 
        Load 
Cap 
Battery 
Cap 
Input 
Voltage
Output 
Voltage
Run
Time
% of
Load
% of 
Battery
Initial  X  V  --  X    V  V         
1
st   X  V  --  X    V    V       
2
nd
  X  V  --  X  V          V   
3
rd  X  V  --  X    V          V 
4
th   X  V  --  X          V     
5th
(return)  X  V  --  X    V  V         
Press>4sec 
(sound disable) 
X  V  V  X    --  --  --  --  --  -- 
Press>4sec 
again(sound enable) 
X  V  X  X  --  --  --  --  --  --  -- 
overload  X  V  --  V    --  --  --  --  V  -- 
“V” illuminated , “X” Not illuminated, “— “ either 
IMPORTANT SAFETY WARNINGS
INSTALLING YOUR UPS SYSTEM
1. Remove two screws and right side 
front panel. 
2. Disconnect the black and red cable.
LCD STATUS DEFINITION
BATTERY REPLAC
E
MENT
8 USB port                                                                                                     . 
USB communication port for management software. 
9. Serial Port                             
Serial port allows connection and communication between the UPS and the 
computer. 
10. SNMP/HTTP Network slot 
Remove the cover panel to install optional RMCARD that allows remote 
monitoring and control UPS on networks. 
11. Site Wire Fault Indicator 
This LED will illuminate to warn the user that a wiring problem exists within 
the AC receptacle, such as a bad ground, missing ground or reversed 
wiring. If illuminated, disconnect all equipment and contact an electrician to 
ensure outlet is properly wired. 
12. EPO (Emergency Power Off) port 
The interface can be used to connect to switches for emergency power off.
BASIC OPERATION
When  you  first  receive  the 
unit,  plug  in  the  unit  to  fully 
charge the battery. 
Unplug the unit and turn Power 
Off  when  first  connecting  your 
computer and peripherals. 
3. Remove two retaining 
screws and pull
out battery cabin.   
.
*Note:Both USB and Serial can not be used simultaneously. 
Install PowerPanel
® Business 
Edition software on the primary 
computer connected to UPS with 
either a serial cable or USB cable.
1  2
3
Specyfikacje produktu
| Marka: | CyberPower | 
| Kategoria: | UPS | 
| Model: | Smart App Sinewave PR500LCDRT1U | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z CyberPower Smart App Sinewave PR500LCDRT1U, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS CyberPower
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         28 Stycznia 2025
                        
                    
                                                            
                        
                         27 Stycznia 2025
                        
                    
                                                            
                        
                         27 Stycznia 2025
                        
                    
                                                            
                        
                         15 Stycznia 2025
                        
                    
                                                            
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         30 Grudnia 2025
                        
                    
                                                            Instrukcje UPS
- Bxterra
- Middle Atlantic
- Dell
- Steren
- Minute Man
- Maruson
- Approx
- East
- Liebert
- Minuteman
- Vanson
- Emerson
- Equip
- GYS
- V7
Najnowsze instrukcje dla UPS
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         2 Kwietnia 2025
                        
                    
                                                            
                        
                         30 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         29 Marca 2025
                        
                    
                                                            
                        
                         27 Marca 2025