Description
Operation
The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- The ledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
- TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellow ledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgota TEST modefeature. Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning. Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16

2
Automatic Transfer Switch, 72x72 DIN Size
Specifications
EquipmentUse Electricalcontrolequipmentforgeneratingsets
Housing&Mounting 72mmx72mmx95mm(includingconnectors)DIN43700plastichousingforpanelmounting
PanelCut-out 69mmx69mm
Protection NEMA4X(IP65atfrontpanel,IP20atrearside)
Weight Approximately0.27kg
EnvironmentalRating Standard,indooratanaltitudeoflessthen2000meterswithnon-condensinghumidity
Operating/Storage Temperature -25ºCto+70ºC/-40ºCto+85ºC
Operating/StorageHumidity 90%max.(Non-condensing)
InstallationOverVoltageCat. IIappliances,portableequipment
PollutionDegree II,Normalofficeorworkplace,non-conductivepollution
ModeofOperation Continuous
EMC EN-61000-6-4,EMCgenericemissionstandardforindustrialequipment
EN-61000-6-2,EMCgenericimmunitystandardforindustrialequipment
ElectricalSafety EN-61010-1,safetyrequirementsforelectricalequipmentformeasurement,controland
laboratoryuse
BatterySupplyVoltage( )Z8-32V max.Operatingcurrentis240mAZ
CrankingDropouts Batteryvoltagecanbe0V formax.100msnduringcranking(batteryvoltageshouldbeZ
atleastnominalvoltagebeforecranking)
MainsVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
GeneratorVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
Display 4Digits,7segmentsLEDdisplayshowing:
MainsVoltage(Phase-PhaseandPhase-Neutral)
AlternatorVoltage.( )
IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1)
ProgramParameters
StatusIndicators TEST ModeLED
MainsContactorClosedLED
GeneratorContactorClosedLED
ContactSensingInputs LoadGeneratorSignal(NO)
EngineRunningSignal(NO)
RelayOutputs RemoteStartRelay(1NO+1NC.12A@32V )Z
MainsContactorRelay(1NC.5A@250V )V
GeneratorContactorRelay(1NO.5A@250V )V
MainsVolgageOkayLED
GeneratorRunningLED
PROGModeLED

3
Automatic Transfer Switch, 72x72 DIN Size
Maximum15mm/0.590inch
83.5mm/3.287inch11.5mm/0.452inch
72mm
72mm
Dimensions
PanelCut-Out
V GENV.L12 VL23 VL31
TEST
PROG
TEST
ATS-10
69mm/2.72inch
69mm/2.72inch
Specyfikacje produktu
Marka: | Emko |
Kategoria: | nieskategoryzowany |
Model: | ATS-10 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Emko ATS-10, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje nieskategoryzowany Emko
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
25 Maja 2024
Instrukcje nieskategoryzowany
- nieskategoryzowany Wachendorff
- nieskategoryzowany Blaupunkt
- nieskategoryzowany Matsui
- nieskategoryzowany Clarion
- nieskategoryzowany S.M.S.L
- nieskategoryzowany Kugoo
- nieskategoryzowany Polaroid
- nieskategoryzowany SereneLife
- nieskategoryzowany Key Digital
- nieskategoryzowany XQ-lite
- nieskategoryzowany Blizzard
- nieskategoryzowany Mauser
- nieskategoryzowany Tesy
- nieskategoryzowany Sanitaire
- nieskategoryzowany Genaray
Najnowsze instrukcje dla nieskategoryzowany
28 Października 2024
28 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024