SYN 50-XH-1 Quick Guide
Overview
Installation
System overview
2.1 Installation requirements
2.2 Installation steps
1: Front panel
2: LED indicator
3: Screw for front cover
4: The main frame body
5: Mounting bracket
6: COM wiring port
7: Generator wiring port(Reversed)
8: Grid wiring port
9: Inverter wiring port
10: Backup wiring port
11: Non-backup wiring port
12: Waterproof plugs
No.
Name
Size
No.
Name
Size
1
straight
screwdriver
Φ2&5mm
2
hammer
/
3
Allen wrench
Φ5mm
4
Cross rise
Φ5mm
5
Electric drill
Φ6mm
6
Wire stripper
/
7
Line pressing
pliers
/
2 3. Required tools
3.1 Wiring instructions
1.Take out the two screws on the front cover of the SYN 50-XH-1, open the front cover, and do not
remove the safety plate inside the machine.
4.Finally, fasten the plastic cover clockwise. Wiring as shown in Figure 3:
3.Route the three power grid cables (L/N/PE) through the three holes and connect them to the power
grid input terminal and the ground copper bar. The screw torque on the power grid terminal is 26.5
in*lbs / 3.0 N*m to 31 in*lbs / 3.5 N*m, and the screw torque on the ground terminal is 13 in*lbs / 1.5
N*m.
2.Loosen the plastic cover printed as " Grid " counterclockwise, remove the three waterproof plugs,
and reserve three holes.
Grid
Generator
Battery
Inverter
Non-backup
Load
The front, back and side pictures of the SYN 50-XH-1 are as follows:
3.Position the mounting bracket against the wall/pole and mark the drilling hole locations.
4.Drill the holes and mount the bracket. Verify that the bracket is firmly attached to the mounting surface.
1.Determine mounting location, on a wall, stud framing or pole.It is recommended to mount it in a location proected from direct SYN 50-XH-1
sunlight.
5.Hang SYN 50-XH-1 on the bracket.
2.To allow proper heat dissipation, maintain at least a 300mm clearance between the SYN 50-XH-1 and other objects.
≥300
≥300
≥300
≥500
3
3
3
33.
.
.
..
Wire specification suggestions
project
Wire diameter
Line length
Grid input cable
6-8AWG
10m
Inverter input cable
8-12AWG
20m
Load output cable
8-12AWG
20m
Generator input cable
6-8AWG
10m
Communication cable
22-26AWG
20m
6-8AWG
10m
L
10mm
10m
6-8AWG
6-8AWG
N
10mm
10m
PE
10mm
Grid and Generator AC cable
20m
8-12AWG
L
10mm
20m
8-12AWG
8-12AWG
N
10mm
20m
PE
10mm
Load and lnverter AC cable
20m
20m
22-26AWG
22-26AWG
10mm
10mm
Communication cable
3.1.1 Connecting SYN 50-XH-1 to the Grid
3.1.2 Connecting SYN 50-XH-1 to the Inverter
When connecting the SYN 50-XH-1 to the XH Inverter, we need to connect AC power cable and communication cable.
2.Route the cables of the three inverters (L/N/PE) through the three holes, connect the cables to the inverter circuit breaker terminal and
the ground copper bar. The screw torque of the inverter circuit breaker terminal is 17.5 in*lbs / 2 N*m, and the screw torque on the ground
terminal is 13 in*lbs / 1.5 N*m.
1.Loosen the plastic cover printed as "Inverter" counterclockwise, remove the three waterproof plugs, and reserve three holes.
3.Finally, fasten the plastic cover clockwise. Wiring is shown as follows:
≤15°
365
92.5
490.3
134.7
120.2
1 2 3 4
5 6
7
Connection to the Grid
2
1)Connecting the AC cable:
1
3
≥300
The above dimensions are in "mm".
PE cables needs to be pressed into the O-type terminal in the accessory bag, as shown in Figure 2.
DC
DC
Backup Load
SYN 50-XH-1
Com
Generator
Grid Inverter
Backup
Load
Non-backup
Load
The system diagram is as follows:
Non-backup
Load panel
Backup
Load panel
Breaker
The above dimensions are in "mm".
AC
AC
AC
AC
PV
AC
AC
6
4
5
7 8 9 10
11
121212
Note:
Note:
Note:
The cable specifications of this SYN 50-XH-1 are as follows, and the wiring end is stripped 10mm.
3
2
1
Grid
Grid
L
N
L
PE
N
PE
Breaker
Specyfikacje produktu
| Marka: | Growatt |
| Kategoria: | Niesklasyfikowane |
| Model: | SYN 50-XH-1 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Growatt SYN 50-XH-1, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Growatt
27 Grudnia 2024
27 Grudnia 2024
17 Grudnia 2024
17 Grudnia 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
Instrukcje Niesklasyfikowane
- Hex
- Planet
- Bulgin
- Shelly
- Christopeit
- Grixx
- Primera
- Janitza
- Be Quiet!
- Disty
- Ubiquiti Networks
- Eurospec
- Supermicro
- Røde
- Carson
Najnowsze instrukcje dla Niesklasyfikowane
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025