Instrukcja obsługi Hager 75040001
Hager
nieskategoryzowany
75040001
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Hager 75040001 (3 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 3 osób i została oceniona przez 2 użytkowników na średnio 4.8 gwiazdek
Strona 1/3

Bus coupling unit flush-mounted
Order-No. : 7504 00 01
Bus coupling unit flush-mounted for B.IQ with thermostat
Order-No. : 7504 00 03
Operation- and
Assembly Instructions
1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons.
Failure to observe the instructions may cause damage to the device and result in fire and
other hazards.
During renovation work, protect the device against soiling through paint, wallpaper
paste, dust, etc. Device can be damaged.
During installation and cable routing, comply with the regulations and standards which
apply for SELV circuits.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
picture 1: Bus coupling unit – front view
Seite 1/3
Bus coupling unit flush-mounted
82503021
97-09462-000 13.08.2010
KNX

picture 2: Bus coupling unit – rear view
(1) Programming LED
(2) Programming button
(3) Application interface
(4) Bus connection
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper
understanding.
The function of this device depends upon the software. Detailed information on loadable
software and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database. Planning, installation and commissioning of the device are
carried out with the aid of KNX-certified software. The latest versions of product database and
the technical descriptions are available on our website.
Intended purpose
- Coupling of flush-mounted application modules to KNX systems
- Installation in appliance box to DIN 49073
4 Information for electrically skilled persons
4.1 Fitting and electrical connection
DANGER!
Electrical shock on contact with live parts in the installation environment.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
Mounting and connecting the device
Observe the installation orientation (picture 1).
o Connect bus cable with connecting terminal (4). Red: +, black: –.
o Install the device in the appliance box.
o If no application module present: mount blank cover.
Seite 2/3 13.08.2010
82503021
97-09462-000
KNX
Bus coupling unit flush-mounted

4.2 Commissioning
Downloading the physical address and application software
The physical address is always assigned for only one device. Only one device may be in
programming mode at any one time.
Application module is not plugged in. Programming button and LED are accessible.
o Press the programming button (2).
The programming LED (1) lights up.
o Assign physical address.
The programming LED goes out.
o Downloading the user software.
i Some application modules, e.g. push-button sensors, require that the application module is
plugged in before downloading. For details, see the corresponding instructions.
o If present: plug in application module with frame. Do not damage the application interface.
5 Appendix
5.1 Technical data
KNX medium TP 1
Commissioning mode S mode
Rated voltage KNX DC 21 ... 32 V SELV
Power consumption KNX
Order-No. 7504 00 01 max. 150mW (with application module)
Order-No. 7504 00 03 max. 200mW (with application module)
Application interface
Power output
Order-No. 7504 00 01 max. 100mW
Order-No. 7504 00 03 max. 150mW
Ambient conditions
Safety class III
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
5.2 Warranty
We reserve the right to make technical and formal changes to the product in the interest of
technical progress.
Our products are under guarantee within the scope of the statutory provisions.
If you have a warranty claim, please contact the point of sale or ship the device postage free
with a description of the fault to the appropriate regional representative.
Berker GmbH & Co. KG
Klagebach 38
58579 Schalksmühle/Germany
Telefon + 49 (0) 2355/905-0
Telefax + 49 (0) 2355/905-111
www.berker.de
Seite 3/3 13.08.2010
82503021
97-09462-000
KNX
Bus coupling unit flush-mounted
Specyfikacje produktu
Marka: | Hager |
Kategoria: | nieskategoryzowany |
Model: | 75040001 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Hager 75040001, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje nieskategoryzowany Hager
15 Sierpnia 2024
15 Sierpnia 2024
15 Sierpnia 2024
15 Sierpnia 2024
15 Sierpnia 2024
15 Sierpnia 2024
14 Sierpnia 2024
14 Sierpnia 2024
14 Sierpnia 2024
14 Sierpnia 2024
Instrukcje nieskategoryzowany
- nieskategoryzowany TP-Link
- nieskategoryzowany KJB Security Products
- nieskategoryzowany Xiaomi
- nieskategoryzowany Napoleon
- nieskategoryzowany RYOBI
- nieskategoryzowany Tenda
- nieskategoryzowany Ravensburger
- nieskategoryzowany Iiyama
- nieskategoryzowany Westfalia
- nieskategoryzowany BaseTech
- nieskategoryzowany Blackmagic Design
- nieskategoryzowany Aluratek
- nieskategoryzowany DeLonghi
- nieskategoryzowany Ernesto
- nieskategoryzowany Holosun
Najnowsze instrukcje dla nieskategoryzowany
28 Października 2024
28 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024