•  Device to be installed only by a qualified 
electrician according to the installation 
standards applicable in the country.   
•  Not suitable for controlling SELV loads.
z
Multi-function Time Switch 
1 Channel Bluetooth
®
6LE005554C
1
Product Presentation
The EGN100 time switch is a clock with weekly and 
annual electronic programming that automatically 
controls different loads. 
Examples of applications: street lighting, neon signs, 
shop windows, monuments, facades etc. 
The integrated astronomical clock can be set to 
switch loads according to sunset and sunrise times.
The EGN100 switch is also compatible with the Hager 
Quicklink radio product line.
The connection of an EEN002 / EEN003 twilight 
sensor (optional) makes it possible to switch the loads 
according to brightness. 
Programming is performed with a mobile terminal  
via Bluetooth
®
 technology using the configuration 
application (iOS and Android) available as a free 
download.
The keys
EGN100
C1/FCT (key and LED) used for: 
• output control; 
•  programming the RF  
module operating mode,
• Bluetooth
®
 reset.
BLE/CFG (key and LED) used for: 
•  Bluetooth
®
 activation and 
deactivation (BLE),
• RF module configuration;
•  Resetting parameters and RF 
modules.
Image 1: Presentation of keys
Main features
• 
Product delivered with updated time and day (Paris).
•  Programming by application via Bluetooth
®
technology:
  - automatic daylight savings time change;
  - astronomical mode;
  - programming by day or group of days;
  - 100 program steps On, Off, pulses 
.
•  Permanent overrides On or Off.
•  Temporary overrides On or Off.
•  Exceptions (temporary, permanent or delayed) can 
be activated remotely using a push button.
•  Twilight switch function via an EEN002 or EEN003 
wired brightness sensor.
Before connecting the cell, or before 
carrying out any operations on it, cut the 
230 V power supply to the clock.
Connection diagram
L
N
1    5    
3    7 
2    6    
4    8    
1  Override input  
or exception
2 Brightness sensor
Figure 2:  EGN100 connection diagram (1 output)
Technical specifications
Electrical specifications
•  Supply voltage: 230 V~ +10/-15%  
and 240 V~ ± 6%
•  Network frequency: 50/60 Hz
•  Consumption: < 170 mW 
•  Output: 1 non-insulated changeover contact with 
a voltage measurement of < 1 V for zero-crossing 
switching.
•  Max. breaking capacity: AC1 μ 10A 230 V~
•  Incandescent light bulbs: 
  -  Power relay with normally open contact/2300 W
  -  Power relay with normally closed contact/1500 W
•  Halogen lamps: 230 V~ 2300 W
•  Fluorescent tubes, compensated // (max. 45 μF): 
  -  Power relay with normally open contact/400 W
  -  Power relay with normally closed contact/300 W
•  Fluorescent tubes, uncompensated, series 
compensated: 1000 W
•  Compact fluorescent lamps and LED lamps: 
  -  Power relay with normally open contact/400 W
  -  Power relay with normally closed contact/300 W
•  Min. breaking capacity: AC1 100 mA 230 V~
•  Rated shock voltage: 4 kV
•   Maximum switching speed at full load: 6 switching 
cycles/minute
Functional features
•  Programming capacity: 100 steps
•  Min. time between 2 steps: 1 minute
•  Precision of operation: ± 0.25 s / day
•  Bluetooth
®
 radio frequency: 2.4 - 2.483 GHz 
  - Max. transmitting power: 10 mW
  - Range: 10 m in free field 
  - Version: 4.2
•  Mobile/PC terminal configuration
  - iOS version equal to or greater than 8
  - Android version equal to or greater than 5.1
  - Windows version equal to or greater than 10
  - Bluetooth
®
: version equal to or greater than 4.2 
•  Quicklink radio frequency: 868 - 870 MHz
  - Max. transmitting power: 25 mW
  - Receiver category 2
  - Range: 100 m in free field 
•  Insulation class: 2
•  Action type: 2B
•  Software class: Class A
•  Ball test T°: 75 °C
•  Upstream protection: 10 A circuit breaker
•  Stated voltage and current for EMC emissions 
testing: 230 V~ / - 0.5 A
•  Protection class: IP20 (case), IP30 (case under 
faceplate)
•  Impact resistance: IK04
Battery
•  Power reserve: 10 years
•  Non-replaceable and non-rechargeable
Case
•  Dimensions: 18 mm / 1 module
•  DIN rail mounted independent product according to 
EN 60715
Environment
•  Operating T° -5 °C to +45 °C
•  Storage T° -25 °C to +70 °C
•  Relative humidity: 95 % to 20 °C
•  Pollution category 2
Connection with screw terminals
• Rigid 0.2 to 4 mm
2
• Flexible 0.2 to 2.5 mm
2
• Screw recess: PH1
Initial set-up
BLUETOOTH
The product must not be in “Quicklink” 
configuration mode.
To program and set the clock with a mobile terminal, 
the Bluetooth
® 
function must be activated.
Each time the BLE key is pressed (> 2 s) the function 
is enabled or disabled.
BLE LED status / Operation
off Bluetooth
®
 disabled
Blue
Bluetooth
®
 enabled
Blue
Bluetooth
®
 assembled and 
connected
Figure 3: LED operation and status
CONFIGURATION APPLICATION
To set the clock, use the application and perform the 
installation as described below.
1. Directly access the application’s download link by 
scanning the   printed on the instructions QR code
with a mobile terminal.
2. Download and install the configuration application.
3. Check that Bluetooth
®
 is enabled (see Initial set-up 
/ BLUETOOTH).
4.  Pair your mobile terminal and your clock via the 
Bluetooth
®
 application.
5. 
Program your product via the application. To do this,
follow the application instructions to configure the 
clock.
Settings via the configuration application:
Settings for the use of your clock are available via the 
application as settings of:
•  date and time;
•  astronomical clock;
•  wired input;
•  daylight savings time change;
•  twilight sensor.
Hager Mood
Additional information is available by 
scanning the displayed QR code with 
your mobile terminal.
EGN100
Specyfikacje produktu
| Marka: | Hager | 
| Kategoria: | Cyfrowy wyłącznik czasowy | 
| Model: | EGK101 | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Hager EGK101, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Cyfrowy wyłącznik czasowy Hager
                        
                         8 Grudnia 2024
                        
                    
                                                            Instrukcje Cyfrowy wyłącznik czasowy
Najnowsze instrukcje dla Cyfrowy wyłącznik czasowy
                        
                         11 Grudnia 2024
                        
                    
                                                            
                        
                         11 Grudnia 2024
                        
                    
                                                            
                        
                         11 Grudnia 2024
                        
                    
                                                            
                        
                         27 Września 2024
                        
                    
                                                            
                        
                         27 Września 2024
                        
                    
                                                            
                        
                         23 Września 2024
                        
                    
                                                            
                        
                         17 Września 2024
                        
                    
                                                            
                        
                         11 Września 2024
                        
                    
                                                            
                        
                         8 Września 2024