Instrukcja obsługi IFM AC2488
IFM
nieskategoryzowany
AC2488
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla IFM AC2488 (7 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 8 osób i została oceniona przez 4.5 użytkowników na średnio 4.3 gwiazdek
Strona 1/7

Operating instructions
AS-i CompactModule M8
AC2488
AC2489
7390940/04 10/2018
UK

2
1 Preliminary note
Technical data, approvals, accessories and further information at
www.ifm.com.
1.1 Safety instructions
• Read this document before setting up the product and keep it during the entire
service life.
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (→ Functions and features).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator.
• The plant manufacturer is responsible for the safety of the plant in which the
device is installed.
• If the device is used in a way that is not intended by the manufacturer, the
protection supported by the device may be impaired.
• Protect units and cables against damage.
1.2 Symbols used
► Instructions
> Reaction, result
Important note
Non-compliance may result in malfunction or interference.
Information
Supplementary note

3
UK
2 Functions and features
• AC2488: 8 inputs CTT3 (AS-i profile S-7.A.A) / AS-interface version 3.0 /
master profile M4 / extended addressing mode: yes / maximum number of
modules per master: 62
• AC2489: 2x4 inputs (AS-i profile 2x S-0.A.E) / AS-interface version 3.0,
backwards compatible / master profile M3 or M4 / extended address mode:
yes / maximum number of modules per master: 31 (2 independent A/B slaves
per module)
3 Installation
► Disconnect power before installation.
► For installation choose a flat mounting surface.
The entire bottom of the module must lie flat on the mounting surface.
► Fix the module onto the mounting surface using M4 screws and washers.
4 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment
must be adhered to.
► Disconnect the installation from power and connect the unit.
To ensure the protection rating:
► Connect the plugs of the sensors to the M8 sockets.
► Tighten firmly, recommended tightening torque 0.3...0.5 Nm.
► Cover the unused sockets with the enclosed protective caps.
► Tighten firmly, recommended tightening torque 0.3...0.5 Nm.
Specyfikacje produktu
Marka: | IFM |
Kategoria: | nieskategoryzowany |
Model: | AC2488 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z IFM AC2488, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje nieskategoryzowany IFM
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
3 Września 2024
3 Września 2024
3 Września 2024
3 Września 2024
Instrukcje nieskategoryzowany
- nieskategoryzowany Berner
- nieskategoryzowany Evolveo
- nieskategoryzowany Eller
- nieskategoryzowany Fujitsu
- nieskategoryzowany Rolls
- nieskategoryzowany Faworyt
- nieskategoryzowany Samsung
- nieskategoryzowany Taurus
- nieskategoryzowany BLANCO
- nieskategoryzowany Hammersmith
- nieskategoryzowany TDE Instruments
- nieskategoryzowany Gabor
- nieskategoryzowany Ilve
- nieskategoryzowany MAK
- nieskategoryzowany Teia
Najnowsze instrukcje dla nieskategoryzowany
28 Października 2024
28 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024