Installation instructions
AS-i bus termination
E70580
7391014/00 06 / 2014
UK
2
1 Safety instructions
Please read the product description prior to set-up of the unit. Ensure that the
product is suitable for your application without any restrictions.
The unit conforms to the relevant regulations and EC directives.
Improper or non-intended use may lead to malfunctions of the unit or to
unwanted effects in your application.
That is why installation, electrical connection, set-up, operation and
maintenance of the unit must only be carried out by qualified personnel
authorised by the machine operator.
2 Functions and features
The passive AS-i bus termination includes two different terminating resistors
(Z1 and Z2) and is used to improve the signal quality for total cable lengths of
100 m.
Three-level voltage monitoring and display for AS-Interface and AUX.
Cable lengths of up to 200 m are possible when the AS-i bus termination is
installed at the point furthest away from the AS-i power supply.
Max. current consumption < 15 mA.
3 Display
Green LED lights: AS-i voltage > 26.5 V DC
Yellow LED lights: AS-i voltage > 18 V DC
4 Installation
Disconnect power.
3
UK
Loosen screw 1 (included) and open the bus
termination.
Choose a flat mounting surface and fix the bus
termination on it (mounting holes 1).
The mounting screws are not supplied.
Preferably place the AS-i cable in the upper
profile slot (2) (terminating resistor Z1).
Should the required signal quality not be sufficient
despite a cable length of up to 200 m, place the
AS-i cable in the lower profile slot (3) (terminating
restistor Z2).
Place the cable correctly in the profile slot.
3
2
The free profile slot can be used for monitoring
the external voltage supply (AUX, black flat
cable).
If the black flat cable is not used, seal the
profile slot with a flat cable blank (E70399).