Operating instructions
Combined sensor for pump diagnosis
and pressure monitoring
PIM693
PIM694
UK
706059 / 00 04 / 2014

2
Contents
1 Preliminary note....................................................................................................3
1. Symbols used 3 ...................................................................................................
2 Safety instructions 3 ................................................................................................
3 Brief instructions 4 ..................................................................................................
4 Functions and features 6 .........................................................................................
5 Function 6 ................................................................................................................
5.1 Processing of the measured signals 6 ..............................................................
5.2 Pump monitoring 7 ............................................................................................
5.3 Pressure monitoring/ analogue function 8 .........................................................
5.4 Pressure monitoring / switching function 9 ........................................................
6 Installation 10 ..........................................................................................................
7 Electrical connection...........................................................................................12
8 Operating and display elements 13 .........................................................................
9 Menu...................................................................................................................14
9. 1 Menu structure 14 ............................................................................................
9. 2 Menu explanation 15 .......................................................................................
10 Parameter setting 16 .............................................................................................
10.1 Parameter setting general 16 ..........................................................................
10.2 Configuring unit for pump diagnosis 18 ...........................................................
10.3 Configuring unit for pressure monitoring 20 ....................................................
10.4 User settings (optional) 21 .............................................................................
10.5 Service functions 22 ........................................................................................
11 Operation 23 ..........................................................................................................
11.1 Read the set parameter values 23 ...................................................................
11.2 Changing the display in the Run mode 23 .......................................................
11.3 Fault indication 24 ............................................................................................
12 Scale drawing 24 ..................................................................................................
13 Technical data ...................................................................................................25
13.1 Setting ranges 26 ............................................................................................
14 Factory setting 27 ..................................................................................................

3
UK
1 Preliminary note
1. Symbols used
►Instruction
> Reaction, result
[…] Designation of buttons, switches or indications
→Cross-reference
Important note
Non-compliance can result in malfunctions or interference.
2 Safety instructions
• Read the product description before installing the unit. Ensure that the product
is suitable for your application without any restrictions.
• Non-adherence to the operating instructions or technical data can lead to
personal injury and/or damage to property.
• Inallapplicationscheckcomplianceoftheproductmaterials(→chapter13
Technical data) with the media to be measured.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
Ampere
AWG (mm2)
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having suit-
able ratings.
Specyfikacje produktu
Marka: | IFM |
Kategoria: | nieskategoryzowany |
Model: | PIM694 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z IFM PIM694, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje nieskategoryzowany IFM
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
4 Września 2024
3 Września 2024
3 Września 2024
3 Września 2024
3 Września 2024
Instrukcje nieskategoryzowany
- nieskategoryzowany Techno Line
- nieskategoryzowany EchoMaster
- nieskategoryzowany Pioneer
- nieskategoryzowany Linksys
- nieskategoryzowany Cellular Line
- nieskategoryzowany Renkforce
- nieskategoryzowany Cleanmaxx
- nieskategoryzowany Arçelik
- nieskategoryzowany Eufy
- nieskategoryzowany Novation
- nieskategoryzowany EasyMaxx
- nieskategoryzowany Sogo
- nieskategoryzowany Steelseries
- nieskategoryzowany Etna
- nieskategoryzowany Pro-Ject
Najnowsze instrukcje dla nieskategoryzowany
28 Października 2024
28 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024
27 Października 2024