Instrukcja obsługi JUNG 2336 REG HZR HE
JUNG
inteligentny dom
2336 REG HZR HE
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla JUNG 2336 REG HZR HE (8 stron) w kategorii inteligentny dom. Ta instrukcja była pomocna dla 18 osób i została oceniona przez 9.5 użytkowników na średnio 4.3 gwiazdek
Strona 1/8

Heating actuator 6-gang, Heating actuator 6-gang with controller
Heating actuator 6-gang
Art. No. : 2336REGHZHE
Heating actuator 6-gang with controller
Art. No. : 2336REGHZRHE
Operating instructions
1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. In so doing, take all the circuit breakers into account, which support dangerous
voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
The load is not electrically isolated from the mains even when the device is switched off.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1: Front view
(1) Supply of electrothermal valve drives
(2) Button field for manual operation
(3) Programming button and LEDs
(4) KNX connection
(5) Connection for mains supply
(6) Status LEDs for outputs
(7) Connection of electrothermal actuators
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
1/8
82590313
j0082590313 20.12.2016

The function of this device depends upon the software. Detailed information on loadable
software and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database. Planning, installation and commissioning of the device are
carried out with the aid of KNX-certified software. The latest versions of product database and
the technical descriptions are available on our website.
Intended use
- Switching of electrothermal actuators for heaters or cooling ceilings
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Switching operation or PWM operation
- Actuators with characteristics opened or closed without power controllable
- Valve drives 230 V or 24 V controllable
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or by bus
- Overload-protected, short circuit-protected, error message with LED
- Protection against jamming valves
- Forced position
- Various setpoints for forced position or emergency operation in case of bus failure for
summer or winter
- Cyclical monitoring of the input signals can be parameterized
- Feedback via bus, e.g. in case of mains failure, overload or sensor failure
- Bus connection with standard bus connecting terminal
iPWM operation: electrothermal actuators only have the positions "open" and "closed". In
PWM operation, switch-on and switch-off during the drive's cycle time achieves an almost
constant behaviour.
Only heating actuators with controllers:
- Integrated room temperature control with setpoint value specification
- Six independent controllers to control up to six independent rooms
- Controller function for heating and cooling operation
Overload protection
In order to protect the device and connected actuators, in case of overload the device
determines which output is involved and switches it off. Non-overloaded outputs continue to
work, which means that the rooms in question are still heated.
- In case of major overloads the actuator initially switches all off the outputs off.A1...A6
- In the case of more minor overloads the actuators switches output groups and/orA1...A3
A4...A6 off.
- The actuator determines the overloaded output in up to 4 test cycles.
- If in the event of only a minor overload it is not possible to unambiguously identify any
output as overloaded, then the actuator switches individual outputs off one after the other.
- The overload can be reported to the bus for each output.
LED display:
- Overload LED flashes slowly: Test cycle active.
- Overload LED flashes quickly: Test cycle completed.
2/8
82590313
j0082590313 20.12.2016
Heating actuator 6-gang, Heating actuator 6-gang with controller

4 Operation
Operating elements
Figure 2: Operating elements – Overview
(6) : Status LEDs for outputsA1...A6
ŋ ŋ1-3, 4-6: Display "Overload/short-circuit" for output group
(8) Button – Manual operationc
(9) LED – On: Continuous manual mode activec
(10) button – Open valveOPEN
(11) LED – On: Valve opened, manual operationOPEN
(12) button – Close valveCLOSE
(13) LED – On: Valve closed, manual operationCLOSE
(14) button – Central operating function for all outputs: Open and close all valveALL OP / CL
alternatively
Status display and output behaviour
The Status LEDs (6) show whether the current flow is switched on or switched off at theA1...A6
appropriate output. The connected heating or cooling valves open and close according to their
characteristics.
Valve drive LED on LED off
Deenergised closed Heating/cooling
Valve opened
Off
Valve closed
Deenergised opened Off
Valve closed
Heating/cooling
Valve opened
- LED flashes slowly: Output in manual mode
- LED flashes quickly: Output disabled via continuous manual mode
Operating modes
- Bus operation: Operation via push-button sensors or other bus devices
- Short-term manual operation: Manual operation locally with button field, automatic return to
bus operation.
- Continuous manual mode: Exclusively manual operation on the device
iNo bus operation is possible in manual mode.
iNo manual mode is possible in case of bus failure.
iThe behaviour after bus failure and return can be set.
3/8
82590313
j0082590313 20.12.2016
Heating actuator 6-gang, Heating actuator 6-gang with controller
Specyfikacje produktu
Marka: | JUNG |
Kategoria: | inteligentny dom |
Model: | 2336 REG HZR HE |
Kolor produktu: | Biały |
Typ produktu: | Mechanizm ogrzewania |
Wbudowany wyświetlacz: | Nie |
Zakres temperatur (eksploatacja): | -5 - 45 °C |
Pobór mocy w trybie czuwania: | 0.4 W |
Napięcie: | 110 - 230 V |
Częstotliwość danych wejściowych: | 50/60 Hz |
Diody LED: | Tak |
Zakres temperatur (przechowywanie): | -25 - 70 °C |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z JUNG 2336 REG HZR HE, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje inteligentny dom JUNG
20 Września 2024
4 Września 2024
30 Sierpnia 2024
23 Sierpnia 2024
22 Sierpnia 2024
20 Sierpnia 2024
19 Sierpnia 2024
16 Sierpnia 2024
16 Sierpnia 2024
14 Sierpnia 2024
Instrukcje inteligentny dom
- inteligentny dom Somfy
- inteligentny dom August
- inteligentny dom Emos
- inteligentny dom Tenda
- inteligentny dom Osram
- inteligentny dom V-TAC
- inteligentny dom Niceboy
- inteligentny dom Blaupunkt
- inteligentny dom Ferguson
- inteligentny dom MAC
- inteligentny dom Asus
- inteligentny dom EQ-3
- inteligentny dom Fanvil
- inteligentny dom Sonoff
- inteligentny dom Aiphone
Najnowsze instrukcje dla inteligentny dom
29 Marca 2025
29 Marca 2025
29 Marca 2025
27 Marca 2025
18 Marca 2025
18 Marca 2025
12 Marca 2025
25 Lutego 2025
19 Lutego 2025
14 Lutego 2025