Instrukcja obsługi Mean Well NDR-75-24
Mean Well
Niesklasyfikowane
NDR-75-24
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Mean Well NDR-75-24 (3 stron) w kategorii Niesklasyfikowane. Ta instrukcja była pomocna dla 18 osób i została oceniona przez 9.5 użytkowników na średnio 3.8 gwiazdek
Strona 1/3

Installaon Manual
Type:
:
:
::NDR DIN rail power supply Series NDR-75,
(
(
(
(( :
:
:
:: 120, 240, 480)
)
)
))
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 6.3A DR 75 12 100 12
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 3.2A DR 75 24 100 24
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 1.6A DR 75 48 100 24
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V A DR 12 100 12 10
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V 5A DR 24 100 24
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V 2.5A DR 48 100 48
NDR-240- INPUT: -240VAC 2.8A 50/60Hz OUTPUT: V A 24 100 24 10
NDR-240- INPUT: -240VAC 2.8A 50/60Hz OUTPUT: V 5A 48 100 48
NDR-480- INPUT: -240VAC 5.3A 50/60Hz OUTPUT: V A 24 100 24 20
NDR-480- INPUT: -240VAC 5.3A 50/60Hz OUTPUT: V A 48 100 48 10
Introducon
NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well DIN series, ’s
they can be mounted on a TS35 Standard DIN rail.
Installaon
( )1 Always allow good venlaon clearances, 5mm le and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheang. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
( )2 The appropriate mounng orientaon for the unit is vercal, the input terminals the bottom and output on at
the top. Mounng orientaons other than that, such as upside down, horizontal, or table-top mounng, is not
allowed.
( )3 Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
7A
10A
15A
20A
Cross-secon of
Lead(mm2 )
0.8
1.3
2.1
3.3
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connecon and the screw terminals are
securely xed to prevent poor contact. If the power supply possesses mul-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
( )4 Use wires that can withstand temperatures of at least 80°C, such as UL1007.
( )5 Recommended wire strapping length m (0.197 . is 5m ”)
( )6 Recommended screwdriver is 3 , sloed type.mm

Installaon Manual
3
1
2
4
( )7 The recommended torque seng for terminals is shown as below.
Mod el
I/P
O/P
N - DR 75
6.9 kgf- (6 -in) cm Lb
6.9 kgf- (6 Lb-in) cm
N - DR 120
10.35 kgf- (9 Lb-in) cm
10.35 kgf- cm (9 Lb-in)
NDR-240
10.35 kgf- (9 Lb-in) cm
10.35 kgf- (9 Lb-in) cm
NDR-480
10.35 kgf- (9 Lb-in) cm
10.35 kgf- (9 Lb-in) cm
( )8 Suggested fuse and maximum number of the SDR PSUs that can be connected to a circuit breaker at 230V are
shown as below.
Model
Fuse
Circuit breaker
C16
D 16
N - DR 75
T3.15A/L250V
6
13
N -120 DR
T4A/L250V
5
10
NDR-240
T5A/L250V
4
10
NDR-480
T8A/L250V
3
5
( )9 Mounng Instrucon:
Mount as shown in gure only, with input terminals down, or else sucient cooling will not be possible.
Admissible DIN rail:TS35/7.5 or TS35/15
For rail fastening :
( )a Tilt the unit slightly rearwards.
( )b Fit the unit over top hat rail.
( )c Slide it downward unl it hits the stop.
( )d Press against the bottom for locking.
( )e Shake the unit slightly to check the locking acon.
( )11 For other informaon about the products, please refer to www.meanwell.com for details.
Warning / Cauon !!
( )1Risk of electrical shock and energy hazard. All failure should be examined by a qualied technician. Please do
not remove the case of the power supply by yourself!
( )2Risk of electric arcs and electric shock (danger to life). Connecng both t primary and the secondary sides he
together is not allowed.
( )3Risk of burn hazard. Do not touch the unit in operaon and shortly aer disconnecon!
( )4 Risk of re and short circuit. The openings should be protected from foreign objects or dripping liquids.
( )5 Only install the unit in a polluon degree 2 environment (Note.1).
( )6 Please do not install the unit in places with high moisture or near the water.
"Click"

Installaon Manual
( )7The maximum operang temperature is for NDR/EDR- - ; 50 for NDR/EDR- -24/48, 45°C 75 12 °C 75
NDR/EDR-120-12/24/48, NDR-240-24/48, NDR-480-24/48, please do not install the unit in places with high
ambient temperature or near re source.
( )8 The FG ( ) must be connected to (Protective Earth). PE
( )9 Output current and output waage must not exceed the rated value on its specicaon.
( )10 Disconnect system from supply voltage:
Before commencing any installaon, maintenance or modicaon work: Disconnect your system from
supply voltage. Make sure that inadvertent connecon in circuit will be impossible!
( )11 For connued protecon against risk of re, replace only with same type and rang of fuse.
Pour ne pas compromere la protecon contre les risqué d’incendie, remplacer par un fusible de même
type et de memes caractérisques nominales.
Note.1: Polluon Degree 2 applies where there is only non-conducve polluon that might temporarily become
conducve due to occasional condensaon. Generally refer to dry, well-venlated locaons, such as
control cabinets.
Manufacturer:
:
:
::
MEAN WELL ENTERPRISES Co., L .TD
No.28, Wuquan 3rd Rd., Wugu Dist.,
New Taipei City 24891, Taiwan
Tel: +886-2-2299-6100
Web: www.meanwell.com
Branch Oce:
:
:
::
China
MEAN WELL (GUANGZHOU)
ENTERPRISES Co., LTD.
2F, A Building, Yuean lndustry Park,
Huangcun,Dongpu Yown, Tianhe
District, Gungzhou, China
Post Code:510660
Tel: +86-20-2887-1200
Web: www.meanwell.com.cn
U.S.A.
MEAN WELL USA, INC.
44030 Fremont Blvd., Fremont,
CA 94538, U.S.A.
Tel: +1-510- -8886 683
Web: www.meanwellusa.com
Europe
MEAN WELL EUROPE B.V.
Langs de Werf 8, 1185XT
Amstelveen, The Netherlands
Tel: + - - -6000 31 20 758
Web: www.meanwell.eu
Specyfikacje produktu
Marka: | Mean Well |
Kategoria: | Niesklasyfikowane |
Model: | NDR-75-24 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Mean Well NDR-75-24, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Mean Well
12 Stycznia 2025
11 Stycznia 2025
11 Stycznia 2025
11 Stycznia 2025
5 Stycznia 2025
3 Stycznia 2025
3 Stycznia 2025
29 Grudnia 2024
12 Grudnia 2024
5 Października 2024
Instrukcje Niesklasyfikowane
- Niesklasyfikowane Jocca
- Niesklasyfikowane Jolin
- Niesklasyfikowane King
- Niesklasyfikowane Cowon
- Niesklasyfikowane IDENTsmart
- Niesklasyfikowane Cayin
- Niesklasyfikowane PS Audio
- Niesklasyfikowane Elektrobock
- Niesklasyfikowane Rainbow
- Niesklasyfikowane WAYDOO
- Niesklasyfikowane Royale
- Niesklasyfikowane Xcellon
- Niesklasyfikowane Smith & Wesson
- Niesklasyfikowane Prenatal
- Niesklasyfikowane Sonuus
Najnowsze instrukcje dla Niesklasyfikowane
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025