–1 – – 2 – – 3 –
P/N: 1802012002011
ioLogik R1200 Series
Quick Installation Guide
Second Edition, April 5 201
Overview
The ioLogik R1200 comes with 2 RS-485 serial ports, which can be
used in one of two ways:
1. For backup or asset monitoring, or
2. As an RS-485 repeater.
The ioLogik R1200 has the industry’s first all- -one design and in
provides Automatic Field Configuration via USB. No technical
background is needed, and maintenance is easy since users can
upload a device’s configuration settings and firmware via USB,
without needing to take a PC to the field site.
Model Selection:
ioLogik
DI
DIO
Relay
AI
AO
R1210
16
–
–
–
–
R1212
8
8
–
–
–
R1214
6
–
6
–
–
R1240
–
–
–
8
–
R1241
–
–
–
–
4
Package Checklist
• 1 ioLogik R1200 series remote I/O product
• Documentation and software CD
• Quick installation guide (printed)
Specifications
System
Serial IO
2 x -485-2W: Data+, Data-, GND RS
(5-contact terminal block)
Protection
8 KV ESD, 1 KV surge, 3 KV EFT
Protocols
Modbus/RTU
Power Input
24 VDC nominal, 12 to 48 VDC
Wiring
I/O cable max. 14 AWG
Dimensions
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight
under 200 g
Operating Temperature
Standard Models: -10 to 75°C (14 to
167°F)
Wide Temperature Models: -40 to 85°C
(-40 to 185°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative
Humidity
5 to 95% (non-condensing)
Altitude
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to
function properly at higher altitudes.
Standards and
Certifications
UL 508, CE, FCC Class A
Warranty Period
5 years (excluding ioLogik R1214*)
Details
See www.moxa.com/warranty
*Because of the limited lifetime of power relay, products that use
this component are covered by a 2-year warranty.
Communication Parameters (Initial mode)
Parity
None, Even, Odd (default = None)
Data Bits
8
Stop Bits
1 2 (default = 1),
Flow Control
None, XON/XOFF (default = None)
Baudrate
1200 to 921.6 kbps (default = 9600)
Digital Input
Sensor Type
NPN, PNP, and Dry contact
I/O Mode
DI or Event Counter
Dry Contact
• On: short to GND
• Off: open
Wet Contact
(DI to COM)
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Isolation
3K VDC or 2K Vrms
Counter/Frequency
2.5 kHz, power off storage
Digital Output
I/O Mode
DO or Pulse Output
Pulse Wave
Width/Frequency
0.1 ms / 5 kHz
Over-voltage
Protection
45 VDC
Over-current Protection
2.6 A (4 channels @650 mA)
Over-temperature
Shutdown
175°C (typical), 150°C (min.)
Current Rating
200 mA per channel
Isolation
3K VDC or 2K Vrms
Relay Output
Type
Form A (N.O.) relay outputs, 5A
Contact Rating
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110
VAC
Inductance Load
2 A
Resistance Load
5 A
Breakdown Voltage
500 VAC
Relay On/Off Time
1500 ms (Max.)
Initial Insulation
Resistance
1G min. @ 500 VDC
Expected Life
100,000 times (Typical)
Initial Contact
Resistance
30 milli-ohms (Max.)
Pulse Output
0.3 Hz at rated load
Analog Input
Type
Differential input
Resolution
16 bits
I/O Mode
Voltage / Current
Input Range
0 to 10 VDC, 4 to 20 mA
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -10 and 60°C
± 0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels)
12 samples/sec
Input Impedance
10M ohms (minimum)
Built-in Resistor for
Current Input
120 ohms
Analog Output
Resolution
12 bits
Output Range
0 to 10 VDC, 4 to 20 mA
Voltage Output
10 mA (Max.)
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -40 and 75°C
Load Resistor
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Installation
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik R1200’s
terminal block terminal; connect the ground from the power V+
supply to the V- terminal. Connect the ground pin ( ) if earth
ground is available.
NOTE
For safety reasons, the wires attached to the power should
be at least 2 mm (12 gauge) in diameter.
Specyfikacje produktu
| Marka: | Moxa |
| Kategoria: | Niesklasyfikowane |
| Model: | ioLogik R1240-T |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Moxa ioLogik R1240-T, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Moxa
11 Stycznia 2025
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
24 Września 2024
Instrukcje Niesklasyfikowane
- Electro Harmonix
- Sureguard
- Kopp
- Rinnai
- Waves
- Bush
- Reflexion
- Slik
- KoolScapes
- Phoenix
- Metabo
- Besco
- Sonnet
- Uni-T
- MJX
Najnowsze instrukcje dla Niesklasyfikowane
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025