1.InstalltheT155withthetwofurnishedmountingscrewstoa
standard2”x4”electricalbox,4-11/16”x2-1/8”squaredevicebox
witha2”x4”adapterringortoa4”x4”boxwithaccessoryadapter
plate.
2.Forwallinstallations,mountthethermostatonaninsidewall
approximately5feetabovetheoor.Thelocationshouldprovide
circulationataverageroomtemperature.Avoiddirectsunlightor
sourcesofhotorcoldairintheroomorwall.
3.Removetheknobandthenthecover.Mountthermostatbase
assemblytotheoutletboxusingthescrewsprovided,tightenthe
screwsevenlybutdonotovertighten.Makewiringconnectionsas
noted.
4.Tousearemotesensor,removejumperJP-1todisablelocal
sensing.FailuretoremoveJP-1whenusingaremotesensorwill
causeimproperoperationofthethermostat.Someunitsdonothave
remotesensingcapability.SeeApplicationNotes.
5.Reinstallthecoverassembly.Installcoverlockingscrewprovided.
Reinstalltheknob.
© Copyright 2010 PECO, Inc. All Rights Reserved P/N 68798 3220-1449 Rev2 Page 1
Installation Instructions
TA155/TB155
Knob Removal and Replacement
InstallatIon
•READTHESEINSTRUCTIONSCAREFULLYBEFOREATTEMPTINGTO
INSTALL,OPERATEORSERVICETHISTHERMOSTAT.
•Failuretoobservesafetyinformationandcomplywithinstructionscould
resultinPERSONALINJURY,DEATHAND/ORPROPERTYDAMAGE.
•Toavoidelectricalshockordamagetoequipment,disconnectpowerbefore
installingorservicing.
•Toavoidelectricshockordamagetoequipment,useonlywiringwithinsula-
tionratedforfullthermostatoperatingvoltage.
•Toavoidpotentialfireand/orexplosiondonotuseinpotentiallyflammableor
explosiveatmospheres.
•Retaintheseinstructionsforfuturereference.Thisproduct,wheninstalled,
willbepartofanengineeredsystemwhosespecificationsandperformance
characteristicsarenotdesignedorcontrolledbyPECO,Inc.Youmust
reviewyourapplicationandnationalandlocalcodestoassurethatyour
installationwillbefunctionalandsafe.
TemperatureRange:50°F-90°F(10°C-32°C)
TA155:AHEAT-OFF-COOLsystemswitchmanuallyselectsheating
orcoolingmode.IntheHEATposition,onlytheheatoutputcycles
withdemand.IntheCOOLposition,onlythecooloutputcycleswith
demand.IntheOFFposition,heatingandcoolingoutputsareoff.Units
withatwopositionsystemswitchorwithoutasystemswitchmustuse
aloadtransferswitchwhenbothheatingandcoolingoutputsareused.
Thispreventscontrolfailureandequipmentdamagecausedbydirect
cyclingbetweenloads.
TB155:AnON-OFFsystemswitchenablesauto-changeoverofheating
andcoolingmodes.IntheONpositionthethermostatactivatesheating
orcoolingoutputsdependantupontherelationshipbetweensetpoint
andambienttemperature.Heatontocoolondeadbandis4°F.In
theOFFposition,heatingandcoolingoutputsareoff.Unitswithout
asystemswitchcyclebetweenheatingandcoolingwitha4°Fdead
band.
FAN:Someunitshaveaswitchformanualselectionoffanspeed.On
theseunitsfanoperationiseitherinternallywiredforfancontinuous
operationorisdependantuponconnectiontothefansupplyinput.
Wheninternallywiredforfancontinuousoperation,thefanwillbe
offwhenthesystemswitchisoff.Whendependantuponexternal
connectionsthefanmaynotbeoffwiththesystemswitchintheoff
position.Thefansupplyinputisswitchedtofanspeedoutputs(HI-
MED-LO).
SWITCHEDPOWER:L1powerisswitchedtothisoutputanytimethe
systemswitchisoutoftheOFFposition.
tHeRmostat opeRatIon
Whenremovingandre-installingtheT-155
knob,caremustbetaken.
•Alignarrowto70°Fontheknob(22C)or
midrangewhenremovingtheknob.
•Reinstallknobbyaligningarrowto70°F
(22C)ormidrange.
•Donotforceit.Whenproperlyaligned,the
knobwillslipintoposition.
Align arrow to 70°F
on the knob (22C)
•UseCopperwire
only,insulateorwire
nutallunusedleads.
•Anywiring,including
theremoteprobe,
maycarrythefull
operatingvoltageof
thethermostat.
caUtIon
▲
!
caUtIon
▲
!
WaRnInG
▲
!

© Copyright 2010 PECO, Inc. All Rights Reserved P/N 68798 3220-1449 Rev2 Page 2
WhitewithOrangeStripe FanHigh
WhitewithRedStripe FanMedium
WhitewithBrownStripe FanLow
Red Heat
Blue Cool
Black L1
Yellow L2orNeutral
Orange SwitchedPower
Violet FanSupply
Brown RemoteProbe1
Brown RemoteProbe2
*Ifapplicable
1.Tousearemotesensor,removejumperJP-1todisablelocalsensing.
2.Remoteprobewiringshouldbelocatedawayfromanyelectrical
motorsorpowerwiring
3.Someunitsareinternallywiredforpermanentfancontinuous
operation.
4.OnunitswithaFanSupplyinputtheoperationofthefanis
determinedbywiringconnection.Forfancontinuous,jumpertheFan
Supplyinput(TB2-5)totheSwitchedPoweroutput(TB3-3).
5.Forfancyclingoperationwithacallforheatorcool,afanrelaymust
beused.
6.Observeelectricalratings.Thermostaticoutputsarepilotdutyonly.
Voltage
Rating
Inductive
FLA LRA
Resistive
Amps
Pilot
Duty
Thermostatic
Switching
24 VAC
120 VAC
240 VAC
277 VAC
N.A. N.A. N.A. 24 VA 10 VA
5.8 34.8 6.0 125 VA 20 VA
20 VA
20 VA
125 VA
125 VA
2.9 17.4 5.0
2.4 14.4 4.2
FAN AND SYSTEM SWITCHES
▲
Specyfikacje produktu
Marka: | PECO |
Kategoria: | termostat |
Model: | TB155-046 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z PECO TB155-046, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje termostat PECO
16 Września 2024
15 Września 2024
15 Września 2024
12 Września 2024
11 Września 2024
10 Września 2024
10 Września 2024
10 Września 2024
8 Września 2024
7 Września 2024
Instrukcje termostat
- termostat Elgato
- termostat Cepra
- termostat Panasonic
- termostat Emmeti
- termostat TrickleStar
- termostat Itho
- termostat Berker
- termostat Vimar
- termostat Techno Line
- termostat Mikoterm
- termostat Danfoss
- termostat Orbis
- termostat Kemot
- termostat Maico
- termostat Tru Components
Najnowsze instrukcje dla termostat
9 Kwietnia 2025
9 Kwietnia 2025
8 Kwietnia 2025
8 Kwietnia 2025
7 Kwietnia 2025
7 Kwietnia 2025
6 Kwietnia 2025
6 Kwietnia 2025
5 Kwietnia 2025
5 Kwietnia 2025