Water Leakage Detector
www.techly.com EN
Introduction
This product is a Water leakage detector, using the princi-
ple of electrode immersed resistor changes to detect water.
The detector adopts MCU intelligent detection, rust-proof
metal probe design with advantages o fhigh accuracy and
sensitivity, low power consumption, long-term stability and
reliability, etc. It can be widely used in all water storage
equipment, such as basement, water tank, machine room,
water route, water tower, water cellar, pools, water room,
solar energy and anywhere to detect water leakage area.
Three optional models: Independent/ Network/ Wireless.
Product Prole
1) LED
2) TEST Button
3) Sensor
(Built-in magnet has
absorbed function)
5-PIN connector instruction (Network type only)
Red: DC Power anode
Black: DC Power cathode
White: COM (relay)
Orange: N.O. (relay)
Yellow: N.C. (relay)
1
2
3
Technical Specication
Type Wireless
Operating voltage DC3V (2x1.5V AA Alkaline Batteries)
Static current ≤10uA
Alarm current ≤40mA ≤50mA
Alarm indicator Red LED and buzzer sounding
Fault indicator Yellow LED
Alarm output 433MHz
Working Temperature 0-60°C
Humidity 0-80%RH (no congelation)
Sound level ≥85db/3M
Hush time 10 minutes
Installation wall mounted or board installed
Dimension 89*89*28mm (bracket not included)
Features
• Rust-proofMetalProbe,LongServiceLife
• SoundandFlashAlarm
• LowPowerConsumptionDesign
• TestandHushButton
• LowBatteryWarning
• MCUProcessing,ResistFalseAlarmEfficiently
• SMTManufactureTechnology,GoodStability
Installation Notice
1. Install the detector where the water is likely to leak.
2. Do not locate the detector in cabinet and other places
where the alarm sound can not came out easily.
3. Do not install it at the area with rain, oil smoke and
steam of cooking range.
4. Do not install the detector with submersed water.
Installation Steps
1. Attachthemountingbracketonthewallorboardfirmly
with screws.
2. Mount the rest ofthe detector into the bracket.
3. Puttheprobeintheoorwherethewaterislikelyto
leak. Or use the sensor magnetic adsorption where re-
quired detects water.
4. Connect the alarm to the power.
Operating Principle
1. Insert 2pcs 1.5V AA batteries into the battery cabinet
(independent or wireless type). Connect DC9-24V power
to 5-pin connector (network type). While the connected
DC power or battery voltage is more than 2.4V, the green
LEDashesoncewithbuzzersounding.Whilethevolt-
ageislessthan2.4V,theyellowLEDashesrapidlyfor
3timeswithbuzzersounding.Thenthedetectorcomes
into normal working status.
2. The green LED long lighting under DC power sup-
ply. While the operated with batteries, the green LED
Specyfikacje produktu
| Marka: | Techly |
| Kategoria: | detektor |
| Model: | I-ALARM Water Leakage Detector |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Techly I-ALARM Water Leakage Detector, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje detektor Techly
21 Września 2024
Instrukcje detektor
- Fluke
- Vimar
- Olympia
- Sun Joe
- Steinberg
- XP
- Thitronik
- V-TAC
- Milwaukee
- Seaward
- Duro
- Vemer
- Edimax
- Multimetrix
- DEDRA
Najnowsze instrukcje dla detektor
30 Marca 2025
28 Marca 2025
21 Marca 2025
14 Marca 2025
11 Lutego 2025
11 Stycznia 2025
8 Stycznia 2025
3 Stycznia 2025
30 Grudnia 2025
30 Grudnia 2025