Instrukcja obsługi Vemer Energy-400 D PWRi
Vemer
Sprzęt pomiarowy
Energy-400 D PWRi
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Vemer Energy-400 D PWRi (1 stron) w kategorii Sprzęt pomiarowy. Ta instrukcja była pomocna dla 18 osób i została oceniona przez 9.5 użytkowników na średnio 4.6 gwiazdek
Strona 1/1

Mod. Energy-400 D PWRi
Energy-400 D PWRi
V3IS00418-011
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: info@vemer.it - web site: www.vemer.it
65
87
45
60
72
L3
L2
L1
N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
PWR/PWRi PWRi
PWRi P1 P2
S1 S2
S1 S2
I
I
L3
L2
L1
+
L3
L1
L2L3
N
L1
L2
+
PWR P1 P2
User Manual
THREE-PHASE ACTIVE ENERGY METER
Read all the instructions carefully
Seriesof4-DINsizestaticmeterstoreadactiveenergyconsumptionin400Vthree-phase
systems
–ENERGY-400DPWRwithcurrentinletthroughshunt
–ENERGY-400DPWRiwithcurrentinletthrough
coils
,withgalvanicisolationbetweenthe
primaryandthesecondary
Connectiontothepowersourceisthroughexternal
ATs
typex/5A
SAFETY WARNINGS
To guarantee correct installation, observe the following instructions:
1) The appliance must be installed by a qualified operator
2) The appliance must be installed in an electrical panel which, after installation,
leaves terminals inaccessible
3) A protection device against over-currents must be installed in the electrical system
upstream of the energy meter
4) Connect the instruments as shown in the diagrams opposite
5) Before making contact with terminals, ensure that conductors to be connected to
the appliance are not live
6) Do not power or connect the appliance if any part of it is damaged
Code Model Description
VE119400 Energy-400 D PWR Three-phaseactiveenergymeter
VE120200 Energy-400 D PWRi Insulatedthree-phaseactiveenergymeter
TECHNICAL SPECIFICATIONS
• Powersupply:3x230(400)VAC(-15%÷+10%),50/60Hz
• InputCurrent:In = 5A; Imax=6A
• Startupcurrent:≤15mA
• Maximumconsumption:3,5VAto400VAC
• Accuracy:class2(EN62053-21)
• Maximumloss: voltagecircuits<2.5VA
powercircuits<2.5VA
• Galvanicisolationbetweenthevoltageinputsandthecurrentinputs(formodel
PWRi only
).
• AmperometricconnectionbyexternalATx/5A
• Display:bywayof7+5digitLCDdisplayunits
• Partialenergyresolution:xed1kWh
• Totalenergyresolution:xed1kWh
• Pulseproperties:Length:100ms±15%
Voltage:9÷24VCC±10%
Maximumoutputcurrent:20mA
• Signalingleds:green=poweron
red=ashingat1/4kWh
yellow=wrongconnection
• Optoinsulatedpulseoutputforremotemeterreading
• Operatingconditions:Temperature:-10÷+45°C
Relativehumidity:10%÷90%noncondensing
• Storagetemperature:-25°C÷+70°C
• Enclosure:4DINsizes
• IngressprotectionratingIP:IP20/IP51onthefront
INSTALLATION
1) Onpoweringthedeviceup,selectthetransformationratioaccordingtotheexternalATx/5A
used.TheATsecondariesofthesolePWRimodelcanbeconnectedtotheearthingsystem
2) Thedevicemustbeconnectedasinthediagram,observingATenergydirection
3) Inorderfortheerrortostaywithinthedevice’sclasslimitsitisnecessarytousethecurrent
transformer in its linear operating range
PROGRAMMING EXTERNAL ATS (X/5A)
SwitchthedeviceonwhileholdingdownthePRGkeyuntilthe
rmwareversionpageappears.
PressthePRGkeytoaccessthepagereadingthedevice’sserialnumber
andthentheATsettingpage.
TherstvaluedisplayedistheATprimary,accordingtothesettingsassignedtothedevice
untilthen.TosettheATvalue,selectthedigitthatneedstobechangedusingthePRGkey.
Whenthedigitselectedashes,changeitusingthearrowkeys and .Therangeof
availablevaluesisfrom0005to1000.ToexittheprogrammingmodeholdthePRGkeydown
foratleast3seconds.IfwhileintheATsettingwindow,nokeyispressedfor30seconds,this
willbeexitedandnochangewillbestored.
Thedefaultfactorysettingis5/5A.
Note: When the AT setting is altered, then the partial energy meter is zeroed, whereas
the total energy meter remains unchanged.
OPERATION
• Whenthedeviceisturnedonthemainpageisdisplayed,representing
thetotalenergycountonthe7-digitupperblockandthepartialenergy
countonthe5-digitlowerblockThemeasuringresolutionforboth
metersis1kWh
• Todisplaythe
total
energycountonly,pressthe key:thismeter
cannot be set to zero
• Todisplaythe
partial
energyreading,pressthe keyagain:this
metercanalsobezeroedmanuallyanytimebyholdingthe“Prg”key
pressedformorethanfourseconds
• Toreturntothemainpagereadingbothmeters(totalandpartial
energy),pressthe keyagain
Pressthe keytoreverttheabovedescribedsequence.i.e.scrollthe
pagesbackward.
Note: The energy value reading refers to the complete three-phase system as an
algebraic addition (Etot
= E1
+E2+E3)
BACKLIGHTING
Backlightingisenabledbydefault:itisswitchedoneachtimethekey
ispressedandstaysonfor30secondsafterthelastkeyispressed.In
ordertoenable/disablethebacklighting,gothe
main page
andhold
the“Prg”keypressedforatleast4seconds:theON/OFFbacklight
statuswillbedisplayedforacoupleofseconds,afterwhichthemain
pagewillreturn.
CONNECTION CHECKS
Whenthedeviceisswitchedon,correctconnectiontocurrentand
voltageterminalsarechecked.Ifconnectionisincorrect,theyellow
LEDlightsupforthreeminutesandthengoesoff.
Atthisstageandduringnormaloperationitispossibletoviewthe
detailedconnectionstatusbyholdingdownthePRGpush-buttonfrom
thetotalmeterpage:theATsettingpage(read-onlyatthisstage)and
theconnectionstatuspagewillthenbedisplayedsuccessively,withthe
possibleerrors(ifany).
Incaseoferrorthefollowingmessagesmayappearonthedisplay:
Connectionerrorononephase(L1inthiscase)
E1 is negative
Connectionerrorontwophases(L1andL2inthiscase)
E1andE2arenegative
Connectionerroronthreephases
E1,E2andE3arenegative
Toexittheerrorreadingpage,pressthePRGkey.
Ifnoerroristobereportedthe“noError“messagewillbereadfora
coupleofseconds.Thenthedevicewillresumenormaloperationfrom
thetotalenergypage.
Note: to restore correct meter operation after an error reading has been displayed,
switch the meter off, connect voltage and current as in the diagrams and then switch
the meter back on.
STANDARD REFERENCES
ConformitytotheEUdirectives:
2006/95/EC
(LowVoltage)
89/336/EEC
modiedby
92/31/EEC
and
93/68/EEC
(E.M.C.)
isdeclaredwithreferencetothefollowingharmonisedstandards:
Safety:
EN61010-1
Electromagnetic compatibility:
EN62052-11andEN62053-21
Dimensions
Connection diagram
Description
ON
PRG
Energy-400 D PWRi
3x230/400V~ 50/60 Hz
In/5(6)A~ cl.2
!
1/4 kWh
imp
Totalenergy
Signaling led
Partialenergy
Pulse output
blocks
Voltage lead
connectionblocks
Setting and
selectionkeys
Current lead
connectionblocks
Main page
Total meter
Partial meter
Backlighting status
Specyfikacje produktu
Marka: | Vemer |
Kategoria: | Sprzęt pomiarowy |
Model: | Energy-400 D PWRi |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Vemer Energy-400 D PWRi, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Sprzęt pomiarowy Vemer
5 Października 2024
2 Października 2024
7 Września 2024
29 Sierpnia 2024
26 Sierpnia 2024
26 Sierpnia 2024
21 Sierpnia 2024
21 Sierpnia 2024
18 Sierpnia 2024
15 Sierpnia 2024
Instrukcje Sprzęt pomiarowy
- Sprzęt pomiarowy Comark
- Sprzęt pomiarowy Ansmann
- Sprzęt pomiarowy Microlife
- Sprzęt pomiarowy Qualita
- Sprzęt pomiarowy Werma
- Sprzęt pomiarowy Sauter
- Sprzęt pomiarowy MSW
- Sprzęt pomiarowy Laica
- Sprzęt pomiarowy Topcom
- Sprzęt pomiarowy BaseTech
- Sprzęt pomiarowy Kyoritsu
- Sprzęt pomiarowy Pioneer
- Sprzęt pomiarowy Atmel
- Sprzęt pomiarowy Testec
- Sprzęt pomiarowy Dahua Technology
Najnowsze instrukcje dla Sprzęt pomiarowy
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025
3 Kwietnia 2025