1AC II
VoltAlert
Instruction Sheet
Read First: Safety Information
 Warning
To prevent possible electric shock or personal injury:
Read all safety information before you use the Product.
Do not rely on the Tester to detect the presence or absence of voltage on a
conductor for safety purposes. A single pole non-contact voltage detector such as
this Tester is NOT suitable to determine if a circuit is hazardous. A volt meter or
2-pole voltage detector is necessary to confirm the absence of hazardous voltage
prior to commencing work
Hold the Product behind the tactile barrier.
Do not use the Product around explosive gas, vapor, or in damp or wet
environments.
Replace all alkaline batteries with fresh batteries of the same manufacturer and type
to prevent battery leakage.
Remove the alkaline batteries if the Product is not used for an extended period of
time, or if stored in temperatures above 50 °C. If the batteries are not removed,
battery leakage may result.
Repair the Product before use if the battery leaks. Battery leakage may create a
shock hazard or damage the Product.
Alkaline batteries contain hazardous chemicals that can cause burns. If exposure to
chemicals occurs, clean with water and get medical aid.
If the Tester is used in a manner not specified by the manufacturer, protection
provided by the Tester may be affected.
Do not use if VoltBeat is not flashing.
Test on a known live source within the rated ac voltage range of the product, both
before and after use to ensure unit is in good working condition.
When using the Tester, if tip does not glow, voltage could still be present. The Tester
indicates active voltage in the presence of AC electric fields of sufficient strength
emanating from the conductor. If the field strength is low, the Tester may not provide
indication of live voltages. Lack of an indication occurs if the Tester is unable to
sense the presence of electric field which may be influenced by several factors the
including, but not limited to:
Shielded wire/cables
Thickness and type of insulation
Distance from the voltage source
Fully-isolated users that prevent an effective ground
Receptacles in recessed sockets/ differences in socket design
Condition of the Tester and Batteries
Do not use if the Tester appears damaged or if the Tester is not operating properly.
Specifically examine the probe tip for cracks or breakage before use. If in doubt,
have the Tester serviced.
Do not apply more than the rated voltage as marked on the Tester.
Use caution with voltages above 30 V ac as a shock hazard may exist.
Comply with local and national safety codes. Use personal protective equipment
(approved rubber gloves, face protection, and flame-resistant clothes) to prevent
shock and arc blast injury where hazardous live conductors are exposed.
Safety: IEC 61010-1: Pollution Degree 2; IEC 61010-2-030: CAT IV 1000 V
Electromagnetic Environment: IEC 61326-1: Portable Electromagnetic Environment;
CISPR 11: Group 1, Class B
Electromagnetic Compatibility: Applies to use in Korea only. Class A Equipment (Industrial
Broadcasting & Communication Equipment)
[1]
[1] This product meets requirements for industrial (Class A) electromagnetic wave equipment
and the seller or user should take notice of it. This equipment is intended for use in business
environments and is not to be used in homes.
Voltage Detection Range:
Model
Region
Range
A1/A2
N. America, S. America, Asia
90 V ac to 1000 V ac
E1/E2
Europe
200 V ac to 1000 V ac
L (low voltage) AC
N. America
20 V ac to 90 Vac
C
China
90 V ac to 1000 V ac
FOR USE BY COMPETENT
PERSONS
Anyone using this instrument should be
knowledgeable and trained about the risks
involved with measuring voltage, especially
in an industrial setting, and the importance of
taking safety precautions and of testing the
instrument before and after using it to ensure
that it is in good working condition.


Specyfikacje produktu

Marka: Fluke
Kategoria: nieskategoryzowany
Model: 1LAC II

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Fluke 1LAC II, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Fluke

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Asko

Asko DBI644MIB.S.TW/1 Instrukcja

28 Października 2024
Asko

Asko DFS233IB.S.TW/1 Instrukcja

28 Października 2024
Emko

Emko EZM-9920 Instrukcja

27 Października 2024
Emko

Emko ESM-3712-H Instrukcja

27 Października 2024
Emko

Emko ATS-10 Instrukcja

27 Października 2024
Emko

Emko EAOM-11.2 Instrukcja

27 Października 2024
Emko

Emko EPM-3790 Instrukcja

27 Października 2024
Emko

Emko EPM-7790 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux IAN 108340 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux HG06009A-BS Instrukcja

27 Października 2024