Introduction
1
1
1
11.
.
.
..
The location of ATS-US in the system
2
2
2
22.
.
.
..
The Auto Transfer Transformer (ATS-US) controls the switch of the contactors to provide power to the critical load stated as EPS Emergency
Power Supply load in both grid-tied and off-grid conditions. There is a contactor in ATS-US to provide user a simple connection. ATS-US is
operating with PCS inverter for the purpose of providing the split phase power when grid accidentally or unexpectedly goes off. This
approach allows the home critical contunously to be supplied.
Configuration
3
3
3
33.
.
.
..
As shown in chart 2.1, the input side of ATS-US is connected with
EPS output of hybrid inverter and grid, the output side is
connected with critical load stated as EPS load. EPS Load is set
default to connect with Grid power.If Grid is lost, EPS Load will
turn the switch to EPS output of hybrid inverter. And there is a
transformer in ATS-US, it can transform 240V to 120/240V split
phase to provide the power to critical load.
AC
Breaker
Breaker
Hybrid Inverter
DC
Breaker
AC
Breaker
Sensor
Load
PV ArrayBattery
EPS Grid
Electrical Grid
ATSE
Load
EPS
Auto transformer
RSD1
Model name
ATS-US
Grid Rated Voltage
240V
Grid Rated Frequency
50 /60Hz
Grid Rated Current
21 a.c.A ,48 a.c.A
EPS Rated Voltage
240V
EPS Rated Frequency
50 /60Hz
EPS Rated Current
21 a.c.A,48 a.c.A
Load Rated Voltage
120/240V
Load Rated Current
21 a.c.A,48 a.c.A
Load Rated power(L-L)
5000VA,11400VA
Load Rated balanced power(L-N)
5000VA,11400VA
Load Rated unbalanced power(L-N)
3000W
Cooling Concept
Natural
Ingress Protection
IP65/NEMA type 4X
Installation
Wall Mountable
Operation Ambient Temperature
- ℃~℃(25+50-13 to+122°F)
Weight
15.6kg/34.3lb
Size
480*275*105mm/18.9*10.8*4.1in
General Information - Parts List
4
4
4
44.
.
.
..
Part List
Item
Item Name
Qty
Item
Item Name
Qty
A
ATS-US (Auto
Transfer
Transformer
1
E
Fixing screws
2
B
User Manual
1
/
/
/
C
Anchor Bolt
3
/
/
/
D
Key
2
/
/
/
Dimension & Weight
5
5
5
55.
.
.
..
Dimension (L x W x H): 480*275*105mm/18.9*10.8*4.1in
Weight: 15.6KG/34.3lb
Tools
6
6
6
66.
.
.
..
NO.
1
2
3
4
Wall Mount Installation
7
7
7
77.
.
.
..
a. Please reserve the space of 300mm (11.81in) from ATS-US.
b. Place the wall bracket horizontally on the wall and mark the
position of 3 holes for screws.
c. Remove the wall mount and drill 3 holes were marked, Drill
holes with φ10 drill Depth: at least 40mm (1.575in).
d. First knock expansion pipe into the hole with Rubber
hammerand then place the wall bracket align with the marked
position on the wall. Last, screw the self-tapping screwing into
the expansion pipe.
e. Tighten the screws on both sides of the wall bracket.
Open the ATS-US
8
8
8
88.
.
.
..
As shown above, please put the key into the Keyhole on the ATS-
US top right and bottom right and clockwise rotation to 90°.The
cover can be opended. Rotate 90 ° counterclockwise to remove the
key. The cover can be pressed directly to close the cover.
(E)
(D)
(A) (C)
(B)
ab
ab
ab
ab
Above aATS 5000T-US,b:ATS 11400T-US :
ATS -US Series Quick Guide
ab

Oceń tę instrukcję

4.1/5 (9 Recenzje)

Specyfikacje produktu

Marka: Growatt
Kategoria: Niesklasyfikowane
Model: ATS-US

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Growatt ATS-US, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Growatt

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Smallrig
Qsc

QSC TSC-8 Instrukcja

29 Stycznia 2025
Xtrarm
Sunding
Xtrarm
Xtrarm
Osee

OSEE TX402 Instrukcja

29 Stycznia 2025