Wireless Smoke Detector
Installation Instructions
1 Overview
The wireless smoke detector features an onboard sounder, a smoke
sensor, an LED indicator and local test capability to allow the user total
visibility of its functionality. It is self-monitoring, alerting the user when
sensor maintenance is needed or batteries are low, and automatically
supervising the radio link.
The EN1244 and EN1244-60 wireless smoke detector have been designed
for operation in the United States; the EN1244A wireless smoke detector
has been designed for operation in Australia; and the EN1244Z wireless
smoke detector has been designed for operation in New Zealand.
The EN1244 wireless smoke detector is intended for open area protection
and for connection to a compatible power supply or control unit for
operation as part of a household re alarm system (UL985).
Note: For UL 2560 installations, refer to the EN6080 Area Control
Gateway Installation Instructions.
1.1 Maximum Number of Repeaters for a UL 2560
Installation
To achieve the 99.99% alarm message reliability required for UL 2560
compliance, system installations must operate within the following limits for
end device and repeater counts.
1.2 Inovonics Contact Information
If you have any problems with this procedure, contact Inovonics technical
services:
E-mail: support@inovonics.com.
Phone: (800) 782-2709; (303) 939-9336.
1.3 Wireless Smoke Detector External Components
Figure 1 Wireless smoke detector external components
Device Indicators
1.4 What’s In The Carton
One 3V-Lithium battery, installed.
Two drywall anchors.
Two mounting screws.
2 Installation and Startup
2.1 Installation Notes
These products are designed to be maintained by professional
security technicians.
Products are tested for indoor use.
All products should be manually tested weekly.
End
Devices
Maximum
Repeaters
150 397
250 386
350 375
500 360
1000 313
2000 238
3000 184
For product and installation videos visit us at
www.inovonics.com/videos or use the QR
code below.
Green LED Red LED Sounder
Power up Both LEDs
blink every 5
seconds
Both LEDs
blink every
5 seconds
Off
Normal
(standby)
Blinks every
10 seconds
Off Off
Sensitivity out of
range
Off Blinks
every five
seconds
Off
Smoke alarm Off Lit Temporal
pattern
Low battery Off Blinks
every 45
seconds
Chirps every
45 seconds
beginning two
days after the
LED begins
blinking
Test
button
Green
LED
Red
LED


Specyfikacje produktu

Marka: Inovonics
Kategoria: czujnik dymu
Model: EN1244
Kolor produktu: Biały
Nadaje się do użytku w pomieszczeniach: Tak
Źródło zasilania: Bateria
Wysokość produktu: 58 mm
Waga produktu: 240 g
Certyfikat środowiskowy (zrównoważonego rozwoju): Federal Communications Commission (FCC), RoHS
Technologia łączności: Bezprzewodowy
Ilość: 1
Zakres temperatur (eksploatacja): 0 - 50 °C
Zakres wilgotności względnej: 0 - 95 %
Rodzaj baterii: CR123A
Diody LED: Tak
Typ mocowania: Montowane na powierzchni
Szerokość pasma: 928 MHz
Czas eksploatacji baterii: 5 lat(a)
Najlepsze zastosowania: Home, Office
Średnica: 134.6 mm
Typ czujnika: Detektor tlenku węgla
Urządzenia alarmujące o decybelach: 85 dB
Interconnectable: Tak
Prąd roboczy: 12 µA

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Inovonics EN1244, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje czujnik dymu Inovonics

Instrukcje czujnik dymu

Najnowsze instrukcje dla czujnik dymu

Elro

Elro FS9010 Instrukcja

2 Kwietnia 2025
Hochiki

Hochiki ALN-V Instrukcja

26 Lutego 2025
Hochiki

Hochiki ACC-V Instrukcja

26 Lutego 2025
Hochiki

Hochiki HCA-4 Instrukcja

26 Lutego 2025
Alecto

Alecto COA-26 Instrukcja

4 Października 2024
Alecto

Alecto SA-100 Instrukcja

4 Października 2024