V3IS00430-011
Mod. CCR
User Manual
CURRENT CONTROL RELAY
Read all the instructions carefully
Current control relay is an electronic control device to be mounted on a panel in a CCR
standard . It operates an external circuit following the set tripping 2-DIN size enclosure
value (direct or alternate current): threshold values, hysteresis and change-over delay can be
adjusted.
SAFETY INSTRUCTIONS
During the installation and operation of the device observe the following instructions:
1) The device must be installed by a qualified person, strictly following the wiring
diagrams.
2) The device must be installed in an electrical panel which, after installation, leaves
terminals inaccessible.
3) Do not power or connect the device if any part of it is damaged.
4) The electrical system in the building where the device is installed must feature a
circuit breaker and an overcurrent protection device.
5) The device is aimed for use in places with over-voltage category III and pollution
degree, 2 as per standards EN 61010-1.
Code Model Description
VE143400 CCR Current-control relay
TECHNICAL SPECIFICATIONS
• Powersupply:230VCA(-15%÷+10%),50/60Hz
• Consumption: 4VA≤
• Termination:6mm
2 metal blocks
• Output:changeovercontactrelay8A/250VAC(resistiveload)
• Inputsignal
–0,15A÷1,5A
–1,0A÷10A
• Fullscaleselectionbywiring(cfr.
Connection diagram
)
• Threshold:tobeadjustedbetween10%and100%ofthefullscalebytrimmer
• Hysteresis:tobeadjustedbetween5%and50%ofthethresholdvaluebytrimmer
• Relayswitchingdelay:tobetrimmer-adjustedfrom0,1to10seconds
• Signallingby2LEDs
– green = power on
– red = relay off (alarm)
• Operatingtemperature:–5°C÷+50°C
• Storagetemperature:–10°C÷+70°C
• Enclosure:2DINsize
• Settingofmaximumorminimumrelaybyselector
• Settingofalarmstatusmemorybywayofselector
• Degreeofprotection:IP20/IP40whencorrectlyinstalledinanelectricalpanel
WIRING
• Powerthedeviceupbyconnectingterminal1tolineandterminal5toneutral.
• Connectthesignaltothemeasuringterminalsaccordingtorange(forusewithDCalso
observe polarity):
–0,15A÷1,5Abetweenterminals2and3
–1A÷10Abetweenterminals2and3,afterterminals3and4havebeenshort-circuited
OPERATION
• Selectmaximumorminimumrelaymodeusingtheselectoronthefrontofthedevice
(>Ir maximum relay, <Ir minimum relay)
• Selectthresholdcurrentusingtrimmer
Sens
• Selecthysteresisvalueusingtrimmer
Hyst
• SelecttheDelayvalueusingthe
Delay
trimmer.Thisisthetimeinterveningbetweenthe
moment Ir is exceeded and the moment the relay switches over
• Selector
memo
enablesthememorystoringfunction.Afteralarmandtheconsequent
relay switch over, the memory function keeps the acquired output status even when the
measured value is back in the useful range; memory is zeroed using the selector, so that
the device does not need to be switched off
RIFERENCE STANDARDS
ConformitytotheEUdirectives:
2006/95/EC(LowVoltage)
89/336/EECmodiedby92/31/EECand93/68/EEC(EMC)
is declared with reference to the following harmonised standards:
Safety:
EN61010-1
Electromagnetic compatibility:
EN61000-6-2,EN61000-6-4
Dimension
Connection diagram
Operating diagram
36 60
45
65
88
Hyst. (%)
Delay (s)
Sens. (%)
on
of f
memo
>
Ir
<
CCR
ON
OFF
Relay
L1
N
1
2
3
4
5
6
7
8
L1
N
1
2
3
4
5
6
7
8
++
>
230V
0V
Sens
Delay
0
6 7 8
6 7 8
<
Ir
Maximum relay mode
Rel ay OFF
Rel ay ON
Delay
Hyst
230V
Sens
0
0V
>
<
Ir
Minimum relay mode
Delay Delay
6 7 8
6 7 8
Rel ay OFF
Rel ay ON
Hyst
Specyfikacje produktu
Marka: | Vemer |
Kategoria: | Niesklasyfikowane |
Model: | CCR |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Vemer CCR, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Vemer
4 Października 2024
3 Października 2024
1 Października 2024
27 Września 2024
22 Września 2024
22 Września 2024
21 Września 2024
21 Września 2024
18 Września 2024
16 Września 2024
Instrukcje Niesklasyfikowane
- Niesklasyfikowane EISL
- Niesklasyfikowane XTRARM
- Niesklasyfikowane Tracer
- Niesklasyfikowane Kernau
- Niesklasyfikowane Intesis
- Niesklasyfikowane TC Helicon
- Niesklasyfikowane Avantree
- Niesklasyfikowane Furrion
- Niesklasyfikowane Vimar
- Niesklasyfikowane Zibro
- Niesklasyfikowane Bruder Mannesmann
- Niesklasyfikowane Socket Mobile
- Niesklasyfikowane Lund
- Niesklasyfikowane KDK
- Niesklasyfikowane UNYKAch
Najnowsze instrukcje dla Niesklasyfikowane
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025