 Power supply connection terminals
 Voltage reading window
 Current reading window
 Parameter setting key
 Metering connection terminals
 36  60 
45 
65 
88 
72  60 
45 
65 
87 
5 
72  75 
72 
66 
L
N
1
2
3
4
5
6
7
8
   COM I V
LOAD
L
N
   COM I V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
LOAD
5 4 3 12
L
N
LOAD
P1P2
P1P2
P1P2
EV2M-2DIN
TRUE RMS
kA
V
A
Prg
Input 5(6)A 600 V~
PRG
A
V
Input 5(6)A~ 600 V~
TRUE RMS
kA
EV2M-4DIN
V
A
kA
EV2M-R
TRUE RMS
Input 5(6)A 600 V~
Prg
User Manual
DIGITAL VOLMETER-AMMETER
Read all the instructions carefully
  The EV2M meters are digital multimeters to measure TRMS values (true 
root mean square values) for alternate voltage and current. It reads these two 
quantities simultaneously on two 3-digit LED displays.
SAFETY WARNINGS
   During the installation and operation of the instrument, proceed in accordance 
with the instructions below:
 1)  The instrument should be installed by a competent operator following the 
installation diagrams carefully
 2)  Before touching the connector terminals make sure that the wires to be connected 
or already connected to the instrument are not live
 3)  The instrument should be installed in a panel from which no access can be gained 
to the terminals after installation
 4)  Do not power or connect the instrument if any part of it is damaged
 5)  The electrical system of the building in which the instrument is to be installed 
should have a switch and a protective device against over-currents
 6)  The instrument is designed for installations with over-voltage category III and 
pollution level 2, in accordance with the EN 61010-1 standard.
 Code  Model  Description
 VE149100  EV2M–2DIN  Voltage-current reading meter 2 DIN
 VE196200  EV2M–4DIN  Voltage-current reading meter 4 DIN
 VE195400  EV2M–R  Voltage-current reading meter 72 x 72
TECHNICAL SPECIFICATIONS
 •  Power supply: 230 V AC (-15%/+10%), 50/60 Hz
   – maximum consumption: 4 VA
 •   Measurement of true root mean square (TRMS) values for voltage and current
•  Voltmeter connection:
   – connection type: direct
   – maximum voltage: VMAX = 600 V
   – maximum consumption: 2,5 VA
•  Ammeter connection:
   – connection type: by AT x/5 A
   – available scales: from 5/5 A to 1000/5 A
   – maximum and nominal current rating: In = 5 A; IMAX = 6 A
   – maximum consumption: 2,5 VA
 •   Reading filter (update speed)
 •  Maximum section of wires: 
   – 6 mm2 for model EV2M-2DIN and EV2M-4DIN
   – 2,5 mm2 for model EV2M-R
•  Operating conditions:
   – operating temperature: –10 ÷ +45 °C
   – relative humidity: 10% ÷ 90% non-condensing
 •  Storage temperature: –20 ÷ +60 °C
 •  Display: 7-segment LED digit display
•  Enclosure:
   – 2 module DIN, RAL 7035 gray for EV2M-2DIN
   – 4 module DIN, RAL 7035 gray for EV2M-4DIN
   – standardized dimensions 72 x 72 mm according to DIN 43700 for EV2M-R
 •  Protection rating: IP51 on the front
RESOLUTION AND ACCURACY
 •  Voltage (full scale V MAX
 = 600 V):
   – Maximum reading: 615 V
   – Minimum reading: 10V
   – Resolution: 1V
   – Accuracy: ± 0,5% full scale ± 1 digit (from 3% to 100% of full scale value)
 •  Current (full scale In = 5 A):
   – Maximum reading: 6 A
   – Minimum reading: 0,02 A
   – Resolution: 0,01 A
   – Accuracy: ± 0,5% full scale ± 1 digit (from 3% to 100% of full scale value)
Note: current data refer to the values provided by the amperometric transformer; 
maximum and minimum readings directly depend on the AT ratio used, whereas 
resolution is dependent on the scale used, as described below.
OPERATION
   During normal operation the device reads the Voltage value (Volts) in the top window and the 
current value (Amperes) in the bottom window.
   The current value is automatically read in the most appropriate scale:
 •  0,01 A resolution in the 0,02 A ÷ 10 A range (e.g.:  )6.47
 •  0,1 A resolution in the 10 A ÷ 100 A range (e.g.:  )39.1
 •  1 A resolution in the 100 A ÷ 1000 A range (e.g.:  )528
 •  10A resolution for values above 1000 A (e.g.: :  )1.03
   In the latter case the value is expressed in kA with the decimal point lit after the first digit and 
the LED point lit to the right of the last digit above the kA symbol
SETTINGS
   After switching the device on it is possible to check and/or change some of the factory settings 
by pressing or holding down the   key according to the procedure described below.Prg
•  Press the Prg key 
The voltage and current reading displays will read a value 
referring to the transformer primary (factory setting: 5).
   To change this value, hold down the   key for at least 2 Prg
seconds until the digits fl ash. Then press and hold the key 
pressed until the desired value is reached (the reading will 
increase by 5-unit steps; 1000 is read as  ).001.
 •  After a few seconds from the moment the key is released, a value 
will indicate the reading fi lter (factory value: 10). The lower this 
value, the faster the readings will be updated, the higher the 
value, the more stable the reading will be.
   To change this value, hold down the   key for at least 2 Prg
seconds until the digits fl ash. Then press the key repeatedly 
until the desired value is set (the reading will increase by 1-unit 
steps; the value range is from 1 to 20).
After one of these parameters is set the device will go off and 
then on again using the new parameters.  The device is reset 
automatically with no need to disconnect it from the power supply.
ERROR MESSAGES
•  Memory error: EEE
   The device has undergone damage that jeopardizes operation
•  Overload error: KKK
   The quantity measured (voltage and/or current) has exceeded the 
maximum admissible value: V > 1,02 x VMAX; I > 1,2 x In.
   Reset is automatic.
REFERENCE STANDARS
Conformity to the EU directives:
2006/95/CE (Low Voltage)
89/336/CEE mod. modified by 92/31/EEC and 93/68/EEC (EMC)
is declared with reference to the following harmonised standards: 
EN 61010-1, EN 61000-6-2 and EN 61000-6-4
Dimensions
Dimensions
Dimensions
Connection
Connection
Connection
Description 
Description 
Description 
Specyfikacje produktu
| Marka: | Vemer | 
| Kategoria: | Niesklasyfikowane | 
| Model: | EV2M-2DIN | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Vemer EV2M-2DIN, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Vemer
                        
                         4 Października 2024
                        
                    
                                                            
                        
                         3 Października 2024
                        
                    
                                                            
                        
                         1 Października 2024
                        
                    
                                                            
                        
                         27 Września 2024
                        
                    
                                                            
                        
                         22 Września 2024
                        
                    
                                                            
                        
                         22 Września 2024
                        
                    
                                                            
                        
                         21 Września 2024
                        
                    
                                                            
                        
                         21 Września 2024
                        
                    
                                                            
                        
                         18 Września 2024
                        
                    
                                                            
                        
                         16 Września 2024
                        
                    
                                                            Instrukcje Niesklasyfikowane
- Denon
- Sissel
- Quigg
- Furrion
- Jupiter
- Urrea
- Wasco
- Fredenstein
- Laney
- CyberData Systems
- RC Allen
- Flavour Blaster
- Portsmith
- Fagor
- Scotsman
Najnowsze instrukcje dla Niesklasyfikowane
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025