RADIOLINK PANEL MODULE
Model: Ei413
RadioLINK Smoke Alarms & Accessories can be
connected wirelessly to Security & Fire Panels
• Powered by 11 - 30VDC from panel
• Can be mounted internally or externally to the panel
• Provides relay outputs (NC, C, NO) from
- Smoke Alarms sensing re
- Alarm fault (Low Battery or Contaminated Chamber)
- CO Alarm sensing CO
• Panel can trigger all smoke / CO alarms to sound
• Unique house coding feature
• Blue LED to facilitate house coding and visual RF transmission
indication
• RF performance to EN300 220-1 in accordance with EN300
220-2
• EMC performance to EN301 489-1 referencing EN301 489-3
• 5 year guarantee
1
House Code Switch
Blue Light
RF Indicator

Security Panel Installation
The Ei413 can be installed in or next to the panel. If the panel
is in a metal case, then the module should be located on the
outside of the panel.
CAUTION!
Before connecting the Ei413 to a re or security panel please
check with the panel manufacturer to determine the correct End
of Line (EOL) device(s) to use and how and where they should
be tted.
PANEL
FIRE RELAY
Alarm In
ANTENNA
NC
NO
C
NC
NO
C
Vin
SW
SW
}
RadioLINK
Alarms &
Controls
J1
NC
NO
C
CO RELAY FAULT RELAY
Voltage eeFr
Contact Input
Voltage eeFr
Contact Input
Voltage eeFr
Contact Input
J1
Dry ntactCo
12V DC
C
NO
11-30VDC Supply
2
Security Panel Wiring Diagram

Check with the panel manufacturers installation manual for
wiring and termination details before proceeding:
1. Each relay of the Ei413 panel module, where used, is wired
to a corresponding contact input in the panel.
2. Check that the sliding jumper link J1 (yellow) is in the off
position. This is the factory default setting.
3. Locate the auxiliary power output in the panel and wire
it to the Vin connector on the Ei413 panel module, being
careful to ensure the polarity of the auxiliary power supply
has been wired correctly.
4. The “Alarm in” signal is optional and can be triggered by an
11 - 30V DC or a dry contact signal from the panel. When
this signal is activated the Ei413 will send out an RF Fire
signal which will activate any RadioLINK alarms or devices
that are in the same housecode.
Fire Panel Installation
CAUTION!
In this application the Fire and Fault relays are being congured
to allow the re panel to indicate a re or fault condition. The
wiring details and end of line (EOL) termination details will
change for different re panels so it is imperitive that you check
the panel manufacturers installation manual before proceeding.
Operation
1. When the Ei413 receives a re signal it will create a short
circuit across the Detector Zone Input, resulting in a re
indication on the panel. A current limiting resistor may be
required so check the panel manufacturers installation
manual.
2. When the Ei413 receives a fault signal it will open circuit
the connection to the Detector Zone Input, resulting in a
fault indication on the panel.
3. A re signal will override a fault signal .
Installation
1. Slide the jumper link J1 (yellow) to the on position. The
factory default setting is off.
2. Locate the auxiliary power output in the panel and wire it to
the Vin connector on the Ei413 panel module.
3. Check that the polarity of the auxiliary power supply has
been wired correctly.
4. Wire the Fault Relay common (C) terminal and the Fire
Relay common (C) terminal to a detector circuit in the
panel.
5. Wire the manufacturers End of Line (EOL) device according
to the re panel installation manual.
6. Power up the re panel and the Ei413 panel module and
follow the manufacturers instructions to set up the re
panel system.
3
Specyfikacje produktu
Marka: | Ei Electronics |
Kategoria: | Niesklasyfikowane |
Model: | Ei413RF |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Ei Electronics Ei413RF, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane Ei Electronics
13 Września 2024
12 Września 2024
9 Września 2024
7 Września 2024
6 Września 2024
28 Sierpnia 2024
16 Sierpnia 2024
15 Sierpnia 2024
15 Sierpnia 2024
6 Sierpnia 2024
Instrukcje Niesklasyfikowane
- Niesklasyfikowane Lumu
- Niesklasyfikowane Lasita Maja
- Niesklasyfikowane Kenton
- Niesklasyfikowane ProForm
- Niesklasyfikowane JBC
- Niesklasyfikowane Smart-AVI
- Niesklasyfikowane Momo Design
- Niesklasyfikowane Crosley
- Niesklasyfikowane Krone
- Niesklasyfikowane Snom
- Niesklasyfikowane Jonard Tools
- Niesklasyfikowane Profoon
- Niesklasyfikowane Muama
- Niesklasyfikowane Hammersmith
- Niesklasyfikowane Insect Lore
Najnowsze instrukcje dla Niesklasyfikowane
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025
29 Stycznia 2025