POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
DIMENSIONS
Do not use device without checking terminal connections.
CONTROLS and OPERATIONS
Capacitor values are recognized and saved with ASEt operation. For doing this, enter
program menu on the device and find ASEt menu. ASEt menu includes 2 parameters
which are   and .S-oF   S-on
When   is selected and SET button is pressed; the device will find and correctS-on
any connection failures (such as wrong connection at voltage and current inputs) first
and then recognize all capacitor steps. If 10th program (PS-10) is selected, all capacitor
powers will be measured. In other programs, only first capacitor step power is measured
and other capacitor steps are calculated and recorded according to selected program.
If    is selected and SET button is pressed during capacitor recognition, automaticS-oF
recognition will be ended.
Note: If there are loads other than compensation on the system, the device may
find the connection after several tries. If the device doesnt complete the automatic
connection process, it cant do the step calculation process. In order to have
correct power values for capacitor steps, current and voltage transformer ratios
must be entered correctly. If current and voltage transformer ratios are not entered,
these ratios are assumed to be 1 and capacitor powers are calculated according
to these values (Refer to VT and CT ratio settings).
          If automatic setup is selected as S-on, automatic mode starts immediately
without waiting to escape from the menu.
Note: A parameter that is calculated automatically by the device can be changed
by the user.
Automatic Capacitor Recognition and Phase Setup Mode
1
For proper operation, current and voltage connections must be connected as
shown in the connection diagram.
After current and voltage terminal connections, capacitor steps connection must
be done according to the connection diagram.
Lastly, computer communication connection must be done.
Do not power-up the device before verifying terminal connections.
1. RG-B/BS Series Connection
a)
b)
c)
d)
Device can detect wrong connection on the way of active power. For correcting connection
fault, automatic setup must be done or suitable phase value must be programmed from AngL
menu, which is for programming phasor angle, from transformer menu. When user does
automatic setup (ASEt), device will open and close 3 phase capacitor in 1st step during
correction of connection failure. Sudden changes in loads and nonlinear loads (Thyristor or
triac controlled frequency inverter, UPS etc.) existing, automatic setup may not be done. In
this condition, user should disconnect the device and restart it and make the same operation.
This operation can do with selecting S-on under ASEt menu. In this case device corrects
the errors and then calculates the capacitor values.If user does not want calculating capacitor
values, selecting S-oF parameter provides this.
User must enter capacitor values after entering current and voltage transformer ratios. Capacitor
values can be calculated automatically or maually. Capacitor powers are measured automatically
by entering S-on under devices ASEt setting (for details please look Operating Mode
Settings). If 10
th
 program (PS-10) is selected in program menu, all capacitor values are
measured by switching on/off of the capacitors in sequence. In this program, 3 phase capacitors
can be connected as desired according to system requirements. If capacitor steps have been
calculated as in the previous step, this step is not necessary. Selecting other program condition
device only calculate 1st step and other steps will be calculated according to selected program.
Device calculates the capacitor values which will be switched ON according to selected
program; so device switches on/off the required steps.
Connection of circuit breaker or automatic fuse between the network and RG-B/BS series
is  highly  recommended.  Circuit  breaker  must  be  in  close  proximity  to  the  device.
All used fuses must be FF type and the current values of the fuses must be 2A or 3A and
6A (Refer to Connection Diagram).
Generator input must be done only when the network is supplied by the generator. Otherwise
device will be switched to the generator position for each generator starts including the
maintaining purpose.
a)
b)
c)
d)
e)
2. 
Commissioning 
RG-B/BS Series
Generator Input
When 110-250 V AC connection is connected to devices generator input, COS1
position will be passive and   will be active. So, compensation will be doneCOS2
according  to  target  COS2  as  long  as  a  voltage  is  present  at  generator  input.
CONNECTION DIAGRAM
Press SET button and enter ASEt menu (S-oF is displayed)
Select S-on option by using UP/DOWN buttons.
(This parameter should be selected as ON in order to start the
Automatic Capacitor Recognition.)
Press SET button in order to activate your selection.
Press SET button 3 sec. and select Auto option.
Select ASEt parameter by using UP/DOWN buttons.
Operating Mode (Automatic/Manual Mode) Settings
RG-B/BS series has two operating modes which are automatic mode and manual
mode. Operating mode can be selected by selecting   (automatic) or A-on A-oF
(manual) option. Manual mode is used for test purpose. In this mode, capacitor steps
are switched on&off to test the relay outputs of the device. In the manual mode,
capacitor steps are switched on by pressing   button and also capacitor stepsSET
are switched off by pressing   button. Factory set values for switching on (ond)ESC
and switching off (oFd) time is 10 seconds. These time values can be programmed
in the Delay (dELy) menu (Refer to delay time setting). In the manual mode, step
numbers, which will be switched on&off, can be programmed in Step menu (Refer
to step number setting). Even if manual mode is selected, after 5 minutes, device
starts to work  in automatic mode  and continues  to operate  in automatic  mode.
When  automatic  mode  is  selected,  AUTO/MAN  LED  lights  on  continuously.
When manual mode is selected, AUTO/MAN LED blinks.
Warning: Device warns user by blinking (short ON, long OFF) the capacitor steps
which will be switched on. Also device warns user by blinking (long ON, short
OFF) the capacitor steps which will be switched off.
For switching capacitors; voltage inputs must be connected and measured
voltage must be higher than (min. 0.5 times) programmed nominal network
voltage.
*  Current value of 3-Fuses, which are connected to protect the capacitors, is
chosen according to the nominal current value of capacitors.
** At 3 phase 4 wire applications L1 and Neutral must be connected devices
voltage measurement inputs, at 3 phase 3 wire applications L2 and L3 phases
must be connected. L1 phases current transformer must be connected to
current measurement input. If load is unbalanced, current cable which is
nearest value of total average value must be connected to current transformer.
In this condition voltage inputs must be set refer to current. When device
programmed to automatic setup, it will program suitable phase angle. So it
will measure true values and true compensation.
*** Communication terminals are only available in BS models.
Precautions for Safe Use and Installation
This user manual is prepared for quick commisioning and operating
of the device. Please read this manual carefully before commisioning
or operating RG-B/BS series
Maintenance, installation and operation of RG-B/BS series must be performed
only by the qualified technicians.
RG-B/BS series is connected to the network with current transformer. Do not
disconnect the current transformer terminals. If you disconnect them, be sure
to short-circuit or connect them to another parallel load which have low impedance.
In case of failure, dangerously high voltage at the secondary side of current
transformer may cause an electric shock.
Device is suitable only for panel mounting.
Verify terminal connections when wiring.
Do  not  use  this  product  for  any  other  purpose  than  its  original  task.
Do not operate undervoltage.
When device  is  connected  to  the  network, do not remove the front  panel.
Do not open the RG-B/BS series housing. There are no user servicable parts
inside it.
Do not clean the device with solvent or similar items. Only clean with a dry cloth.
Electrical  equipment  should  be  serviced  only  by  your  competent  seller.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
No responsibility is assured by the manufacturer or any of its subsidiaries
for  any  consequences  arising  out  of  the  use  of  this  material.
1   Panel cut-out dimension must be 91 mm x 91 mm for Type PR19 and 143 mm x)
143 mm for Type PR16.
2)  Before installation, remove the mounting brackets.
3)  Mount the device to front panel.
4)  Insert the mounting brackets.
5)  Wire thickness for voltage and current terminals must be 2,5 mm
2
, but it is suitable
for cables which have up to 4 mm
2
 section.
6)  CAT5 cable is recommended for RS-485 input terminal.
Excessive force can damage the device.
Turn the screw into the terminals and tighten until the RG-B/BS series is secured
in place.
     70mm
     79.3mm
90mm
     96mm
96mm
Type PR 19
15 17 18 19 20 21 22
5 6 9 10
6A
Alarm Relay
11 12
C1 C6 C7 C12
23 24 25 26 27 30 31 32 33
N
L3
L2
L1
Fan Relay
13 14
1 2 3 4
Un V
in
I
in
Generator
Input
110~250 V AC
16
1A
K L
l1k1
~ ~
L2
L3
**
**
Type
 PR16
(144x144)
143
99
121
138.4
143
18
34.5
67
RG-6B/BS
RG-8B/BS
****
Voltage Measurement
Input
Auxiliary
Supply
Current Measurement
Input
Generator
Input
Fan Relay
Alarm Relay
RG-12B/BS
RG-6B/BS
RG-8B/BS
TR B GNDA
RS485
Specyfikacje produktu
| Marka: | ENTES | 
| Kategoria: | Niesklasyfikowane | 
| Model: | RG-8BS-96 | 
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z ENTES RG-8BS-96, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Niesklasyfikowane ENTES
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         3 Stycznia 2025
                        
                    
                                                            
                        
                         27 Grudnia 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            
                        
                         8 Października 2024
                        
                    
                                                            Instrukcje Niesklasyfikowane
- Danfoss
- SuperTooth
- Könner & Söhnen
- ZAZU
- Cylinda
- Nilox
- Trimble
- Monogram
- Hover-1
- Universal Remote Control
- Watercool
- Propellerhead
- Eura
- Ovation
- Sinbo
Najnowsze instrukcje dla Niesklasyfikowane
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025
                        
                    
                                                            
                        
                         29 Stycznia 2025