Push-button interface 2-gang plus
Art. no. MTN670802
Push-button interface 4-gang plus
Art. no. MTN670804
¼
DANGER
Risk of fatal injury from electrical current
.
All work on the device should only be carried out
by trained and skilled electricians. The country-
specific regulations and the valid KNX guidelines
must be followed.
½CAUTION
The device could become damaged.
- Only operate the device according to the
specifications stated in the Technical data.
- High voltages can cause damage. Never
connect the device to 230 V!
The push-button interface for KNX has two (art. no.
MTN670802) or four (art. no. MTN670804) inputs and
outputs. The inputs can be used to establish binary
statuses (via floating contacts) and the outputs can be
used to activate control lamps (low current LEDs).
For example, by connecting floating push-buttons or
switches to the inputs, you can use the KNX to perform
a range of functions including switching, dimming,
operating blinds and retrieving scenes, etc.
To check statuses, you can connect control lamps (low
current LEDs, e.g. in the switch) to the outputs and
activate them via KNX.
The contact supply voltage (SELV) for the connected
buttons/switches and the control lamps comes from
the push-button interface.
The push-button interface has a bus coupler.
For your safety
Push-button interface introduction
E1E2
E3E4A1A2A3
WH WHWHWH
BUBNGN
GD
BUBNGN
RD GY
A4
RD
A Bus connection
B Programming button
C Programming LED
1 Mount the push-button interface in
a flush-mounted box at least 40 mm deep,
a cavity wall installation box (Ø = 60 mm),
a junction box.
2 Connect inputs to a floating push-button or switch
(see connection example).
3 Connect outputs to control lamps (low-current
LEDs) in the push-button or switch (see connection
example).
Connection example:
* (only art. no. MTN670804)
¼
WARNING
Risk of fatal injury from electrical current.
The device could be damaged.
Safety clearance must be guaranteed in
accordance with IEC 60664-1. There must be at
least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
4 Connect the bus wires to the bus connecting
terminal.
5 Connect the bus terminal to the bus connection
A.
Operating and display elements
Push-button interface installation
Colour coding of the incoming cables
GD grey: Reference potential (GD)
E1 blue: Input 1
E2 brown: Input 2
E3 green: Input 3 *
E4 red: Input 4 *
A1 white/blue: Output 1
A2 white/brown: Output 2
A3 white/green: Output 3 *
A4 white/red: Output 4 *
E1E2E3E4A1
A2
A3
WH WHWHWH
BUBNGN
GD
BUBNGN
RD GY
A4
RD
A
B
C
KNX
+ -
E 1
E 2
E 3
E 4
A 1
A 2
A 3
A 4
GD
230 V
4 mm
KNX
A
1 Press the programming button.
The programming LED lights up.
2 Load the physical address and the application into
the device from the ETS.
The application was loaded successfully, the device is
ready for operation.
If you have technical questions, please contact the Cus-
tomer Care Center in your country.
www.schneider-electric.com
This product must be installed, connected and used in
compliance with prevailing standards and/or installati-
on regulations. As standards, specifications and de-
signs develop from time to time, always ask for
confirmation of the information given in this publicati-
on.
Schneider Electric Industries SAS
Putting push-button interface into
operation
Technical data
Initialisation: The push-button interface
is only ready for operation
after at least 17 seconds
after a bus voltage failure or
a bus reset.
Power supply from bus: DC 24 V/< 10 mA
Inputs
Use: connection of floating
contacts
Contact resistance: < 500 Ω
(with closed contact)
Outputs
Use: connection of low-current
LEDs (< 1 mA)
Contact voltage V k : < 3 V (SELV)
Contact current: < 0.5 mA
Ambient temperature
Operation -5 °C to +45 °C
Storage -25 °C to +55 °C
Transport -25 °C to +70 °C
Max. humidity: 93 % relative humidity, no
moisture condensation
Environment: The device is designed for
use at a height of up to
2000 m above sea level
(MSL).
Protection class: II
Type of protection: IP 20
Connections
Inputs, outputs:
Art. no. MTN670802 each 2 and GD,
single-core
Art. no. MTN670804 each 4 and GD,
single-core
Maximum cable length: 7.5 m
Push-button interface plus
Operating instructions
E1E2
E3E4A 1A2A3
WH WHWHWH
BUBNGN
GD
BUBNGN
RD GY
A4
RD
V6708-561-00 01/08
1


Specyfikacje produktu

Marka: Schneider
Kategoria: Niesklasyfikowane
Model: MTN670804

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Schneider MTN670804, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Schneider

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

SmallRig

SmallRig VB99 SE Instrukcja

29 Stycznia 2025
QSC

QSC TSC-8 Instrukcja

29 Stycznia 2025
XTRARM

XTRARM XTR-FS5130 Instrukcja

29 Stycznia 2025
Sunding

Sunding SD-581G Instrukcja

29 Stycznia 2025
XTRARM

XTRARM XTR-FS5070 Instrukcja

29 Stycznia 2025
XTRARM

XTRARM XTR-FS2010 Instrukcja

29 Stycznia 2025
OSEE

OSEE TX402 Instrukcja

29 Stycznia 2025